background image

Pastry Display Cases

  Models:  CURP series 

CURLP

CURHP

CURP

Instruction Manual

Tel : 416-663-3051  Fax : 416-663-5793
Toll Free : 1-888-408-8819

124 Norfinch Dr. Toronto, ON. M3N 1X1   

 REFRIGERATION LTD.

Содержание CURHP2

Страница 1: ...Pastry Display Cases Models CURP series CURLP CURHP CURP Instruction Manual Tel 416 663 3051 Fax 416 663 5793 Toll Free 1 888 408 8819 124 Norfinch Dr Toronto ON M3N 1X1 REFRIGERATION LTD...

Страница 2: ...n 9 5 MAINTENANCE 12 5 1 Cleaning and maintenance 12 6 SERVICE 14 6 1 Faults identification and repair 14 6 2 Service 15 List of Figures Figure 1 CURP 4 Figure 2 placing the hooks in the frame 6 Figur...

Страница 3: ...ption of the unit CURP series display cases have a dynamic cooling system All units are equipped with automatic condensate evaporation and automatic defrosting The electronic thermostat cooperates mod...

Страница 4: ...egs 11 Serial plate 12 Control panel thermostat switches 2 3 Technical data Table 1 Technical data Model Voltage V Hz Ph Rated Current A Max shelf load lbs kg Weight lbs kg CURP2 115 60 1 8 max fuse 1...

Страница 5: ...e protection efficiency with results of measures performed according to binding regulations 3 2 Unit Location Remove cardboard angles and protective foil Install the unit on a strong and leveled surfa...

Страница 6: ...turning it on The unit should be cleaned with warm water not exceeding 40 C with a neutral detergent For washing and cleaning the equipment it is prohibited to use products containing chlorine and sod...

Страница 7: ...ck and place it in the suitable position and at the suitable angle 7 Acorn nut of the screw 8 Silicon pad 9 Plasticizer pad 10 Screw 11 Inner frame 12 Display glass shelves of the frame 13 Bumper pads...

Страница 8: ...quipment and shall ensure proper water condensate outflow during defrosting After transporting the equipment wait about 2 hours before starting up the unit To ensure proper conditions for the stored p...

Страница 9: ...when the actuation of the ventilators is delayed by external disengagement or when another procedure is in progress Diode 3 Defrosting This symbol is visible when the defrosting function is activated...

Страница 10: ...ter error manual Ed not active ON defrost ended by timeout On first defrost ended correctly CHt active ON dirty condenser alarm manual MODIFYING THE PARAMETERS Parameter navigation The operating param...

Страница 11: ...st temperature set point 12 0 C 50 130 dP maximum defrost duration 30 min 1 199 d4 defrost when switching the instrument on 0 0 1 d5 defrost delay on power up or when enabled by digital input 0 min 0...

Страница 12: ...with warm water and mild soap Make sure to cover the fan motor to prevent moisture damage Dore gaskets shelves and supports should be cleaned on a regular basis Fan blades and guards should be cleaned...

Страница 13: ...d to use vacuum cleaner or compressed nitrogen to suck blow the dirt from between lamellas The seller shall not be held responsible for any condenser damages in the case of non observance of condenser...

Страница 14: ...ty the condensate container The equipment does not reach the proper temperature the light is on Make sure that The main switch is on Temperature setting on the thermostat is properly set Thermostat wo...

Страница 15: ...cuit This phenomenon constitutes a technical feature of cooling devices and does not signify equipment failure Steam precipitation on glasses is normal in the event of high relative air humidity excee...

Отзывы: