Fluid monitoring system - Application solution
UK
5 Installation
►
Disconnect the power of the machine before installation�
►
Adhere to the instructions enclosed to the individual devices�
5.1 Fluid monitoring system
►
Mount the fluid monitoring system in the cooling water process�
► Adhere to the flow direction during installation (black arrow mark).
5.2 IO-Link master
►
Fix the IO-Link master to a flat installation surface�
►
Use 2 M5 mounting screws and washers for fastening�Tightening torque: 1�8 Nm�
5.3 Power supply
►
Integrate the power supply into the control cabinet� The following has to be observed:
– Suited for DIN rails according to EN 60715 with a height of 7�5 or 15 mm�
– Align the input terminals downwards�
– In case of continuous full load adhere to the following installation distances:
Left / right: 5 mm (15 mm for adjacent heat sources)
Top: 40 mm, bottom 20 mm from the device�
The device is rated for convection cooling�
►
Do not impede the air circulation� Adhere to installation distances�
5.4 Industrial PC
►
Install the industrial PC in the control cabinet, taking the following into account :
– Mount the industrial PC on a flat mounting surface�
– Use 4 M5 mounting screws and washers for fastening�
The device is rated for convection cooling�
►
Do not impede the air circulation� Adhere to installation distances�
6 Electrical connection
The unit must be connected by a qualified electrician�
►
Observe the national and international regulations for the installation of electrical equipment�
►
Adhere to the instructions enclosed to the individual devices�
►
Disconnect power�
1� Connect the sensors of the fluid monitoring system to the IO-Link master�
2� Connect the IO-Link master to the secondary side of the power supply�
3� Connect the IO-Link master to the Ethernet interface 1 of the industrial PC via the IoT interface�
4� Connect the industrial PC to the secondary side of the power supply�
5� Connect the primary side of the power supply unit to the voltage supply�