SmartPLC DataLine with EtherNet/IP device interface
179
>
Details of the diagnosis area
41581
>
Diagnosis - System diagnosis
41448
Offset
Word no.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
n
-
-
-
-
-
-
-
-
-
-
-
-
PS
GI
OT
ISE
Legend:
Flag
Description
ISE
Internal System Error Interner Systemfehler
OT
over temperature: temperature inside the device has exceeded the permissible max. temperature value
GI
gateway inactive: the gateway mode was deactivated
PS
PLC stop: The controller was stopped
>
Diagnosis - AS-i diagnosis
41466
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
n
-
-
PF19 PF22.5 EF
S0
PM
IME
-
-
-
DAE
PE
CEIP
CEAS CEMS
n+1
Voltage AS-i+ to AS-i- in mV
n+2
Voltage FE to AS-i- in mV
n+3
Symmetry in % (-100% ... +100%)
Legend:
Flag
Description
IME
internal master error: Internal system error of an AS-i master
PM
projection mode: AS-i master was set to the projection mode.
S0
slave 0 detected: New slave 0 was detected.
EF
earth fault: Earth fault was detected
PF22.5
22.5V AS-i Power-Fail (classic AS-i Power) was detected.
PF19
19 AS-i Power-Fail (Power24) was detected.
CEMS
Configuration Error
– Missing Slave: AS-i configuration error, one or several slaves are projected, but not
available.
CEAS
Configuration Error
– Additional Slave: AS-i configuration error, one or several slaves are available, but
not projected.
CEIP
Configuration Error
– Invalid Profile: AS-i configuration error, the slave profiles of one or several slaves
differ from the projected slave profiles.
PE
periphery error: One or several AS-i slaves have a periphery error.
DAE
duplicate address error: One or several multiple-addressing faults occurred.