SmartPLC DataLine with EtherNet/IP device interface
111
>
6.6
Set Ethernet configuration interfaces
42937
To configure the Ethernet configuration interfaces 1 (X3) and 2 (X8):
Ethernet configuration interface 1 (X3):
►
>
►
Select [IP setup].
►
Set interface parameters (→
Notes on IP settings
Ethernet configuration interface 2 (X8):
►
>
►
Select [IP setup].
►
Set interface parameters (→
Notes on IP settings
>
6.7
Exchange AS-i slave
41506
AC1423/24 makes it possible to replace an AS-i slave by a new AS-i slave in the operating mode
"protected mode".
Requirements:
>
The new and the old AS-i slave have the same device profile(→
Profiles of AS-i slaves
>
The new AS-i slave has the address
0
.
>
Parameter [Automat. adressing] is activated (→
Set the monitoring functions of the AS-i master
1 Remove old AS-i slave
►
Disconnect the AS-i slave to be replaced from the AS-i network
>
AC1423/24 detects a configuration error and generates a corresponding OSC message.
2 Install new AS-i slave
►
Connect the new AS-i slave to the AS-i network.
>
AC1423/24 detects the new AS-i slave and automatically assigns the address of the old AS-i slave.
>
The OSC error message disappears.
>
The new AS-i slave is operational.