10.3.6 Deactivation of the counter reset
►
Select [rTo] and set OFF�
> The meter is only reset after overflow (= factory setting)�
10.3.7 Counter reset using an external signal
►
Select [ou2] and set In�D�
►
Select [DIn2] and set the counter reset signal:
HIGH = reset for high signal
LOW = reset for low signal
+EDG = reset for rising edge
-EDG = reset for falling edge
10.4 Settings for temperature monitoring
10.4.1 Limit monitoring temperature (OUT2)
►
Select [SEL2] and set TEMP�
►
Select [ou2] and set the switching function: Hno, Hnc, Fno or Fnc�
►
Select [SP1] and set the upper temperature limit�
►
Select [rP2] and set the lower temperature limit�
10.4.2 Analogue output temperature (OUT2)
►
Select [SEL2] and set TEMP�
►
Select [ou2 ] and set the analogue function: I (4���20 mA) or U (0���10 V)�
►
Select [ASP2] and set the temperature value at which the minimum current or voltage
value is provided�
►
Select [AEP2] and set the temperature value at which the maximum current or voltage
value is provided�
10.5 User settings (optional)
10.5.1 Standard unit of measurement for volumetric flow
►
Select [uni] and set the unit of measurement�
The setting only has an effect on the volumetric flow value� The consumed quantity
(meter reading) is automatically displayed in the unit of measurement providing the
highest accuracy�