10.1.2 Locking / unlocking
The unit can be locked electronically to prevent unintentional settings� On delivery:
not locked�
Locking is also possible via an IO-Link capable parameter setting tool�
Locking
►
Make sure that the unit is in the normal operating mode�
► Press [▲] and [▼] simultaneously for 10 s until [Loc] is displayed.
Unlocking
►
Make sure that the unit is in the normal operating mode�
► Press [▲] and [▼] simultaneously for 10 s until [uLoc] is displayed.
10.1.3 Timeout
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged parameter�
10.2 Settings for volumetric flow monitoring
10.2.1 Switch Point monitoring of volumetric flow (OUT1)
►
Select [OU1] and set the switching function: Hno, Hnc, Fno or Fnc�
►
Select [SP1] and set the Switch Point limit value of the volumetric flow�
►
Select [rP1] and set the Reset Switch Point limit value of the volumetric
flow�
Main menu:
[OU1]
[SP1]
[rP1]
10.2.2 Switch Point monitoring of volumetric flow (OUT2)
►
Select [SEL2] and set FLOW�
►
Select [OU2] and set the switching function: Hno, Hnc, Fno or Fnc�
►
Select [SP2] and set the Switch Point limit value of the volumetric flow�
►
Select [rP2] and Reset Switch Point lower limit of the volumetric flow�
Menu CFG:
[SEL2]
Main menu:
[OU2]
[SP2]
[rP2]
10.2.3 Analogue output flow rate (OUT2)
►
Select [SEL2] and set FLOW�
►
Select [OU2 ] and set the analogue function:
I (4���20 mA) or U (0���10 V)�
►
Select [ASP2] and set the volumetric flow value at which the minimum
current or voltage value is provided�
►
Select [AEP2] and set the volumetric flow value at which the maximum
current or voltage value is provided
Menu CFG:
[SEL2]
Main menu:
[OU2]
[ASP2]
[AEP2]