4.5 Switching function
OUTx changes its switching status if it is above or below the set switching limits
(flow or temperature)� Hysteresis or window function can be selected� Example of
volumetric flow monitoring:
Hysteresis function
Window function
SP
rP
SP = set point
rP = reset point
HY = hysteresis
Hno = hysteresis NO (normally open)
Hnc = hysteresis NC (normally closed)
SP = upper limit
rP = lower limit
FE = window
Fno = window NO (normally open)
Fnc = window NC (normally closed)
When the hysteresis function is set, the set point [SP] is defined first and
then the reset point [rP] which must have a lower value� If only the set
point is changed, the reset point is changed automatically; the difference
remains constant�
When set to the window function, the upper limit [SP] and the lower limit
[rP] have a fixed hysteresis of 0�25 % of the final value of the measuring
range� This keeps the switching status of the output stable if the flow rate
varies slightly�