7.3 Restore the factory setting (reset)

 

► Press the pushbutton   for at least 15 s�

 

> LED 9 lights, after approx� 5 s it flashes�

 

> After approx� 15 s LEDs 0���9 flash orange� 

 

► Release the pushbutton� All settings are reset to the factory setting:

 -operating area: 5 ���100 cm/s for water

 -switch point: LED 7

 -output function: NO

 -unlocked�

7.4 Lock / unlock the unit

The unit can be locked electronically to prevent unintentional settings�

 

► Press both setting pushbuttons simultaneously for at least 10 s in the operating 

mode� 

 

> The indication goes out, the unit locks or unlocks� 

On delivery: unlocked�

8 Error during adjustment

If no adjustment is possible, all LEDs flash red� The unit then passes into the 

operating mode with unchanged values�

Possible cause /aid:

Error during installation�

 

► Read chapter 3 Installation� 

Check whether all requirements have 

been met�

The difference between maximum flow and 

minimum flow is too small�

 

► Increase the flow difference and carry 

out the adjustment once again�

The sequence high flow /low flow adjust-

ment was not adhered to�

 

► Carry out the two adjustment operations 

again in the right sequence�

Содержание SI 5001

Страница 1: ...Operating instructions Flow monitors SI5000 SI5001 11458744 00 08 2010 UK...

Страница 2: ...n 6 4 Electrical connection 7 5 Operating and display elements 7 6 Set up and settings for water 8 6 1 Change the switch point optional 8 6 2 High flow adjustment optional 9 7 Additional settings opti...

Страница 3: ...roper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connection set up operation and mainte nance of the unit...

Страница 4: ...n applies output open if medium is flowing If the flow speed increases the switching status changes when the switch point is reached If the flow speed falls again the switching status changes if the v...

Страница 5: ...ation location General The sensor tip is to be completely sur rounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pip...

Страница 6: ...ces of interference 3 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the threads...

Страница 7: ...ct the unit as follows A SI5000 positive switching B SI5001 negative switching Core colours of ifm sockets 1 BN brown 3 BU blue 4 BK black 5 Operating and display elements 1 Operation display The gree...

Страница 8: ...2 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 2 You can restore the factory setting any time 7 3 6 1 Change the switch point optio...

Страница 9: ...you should additionally adapt the unit to the minimum flow Note The following adjustment must only be carried out after the high flow adjust ment Let the minimum flow circulate in the installation or...

Страница 10: ...taneously for at least 10 s in the operating mode The indication goes out the unit locks or unlocks On delivery unlocked 8 Error during adjustment If no adjustment is possible all LEDs flash red The u...

Страница 11: ...the representation range LED 0 flashes current flow far below the represen tation range Interference indicators Short circuit at the switching output The operating indicator and red LEDs light alterna...

Страница 12: ...on 3 tightening torque 25 Nm 12 Technical data Application area Liquids and gases Operating voltage V 19 36 DC1 Current rating mA 250 Short circuit protection pulsed reverse polarity overload protecti...

Страница 13: ...ating IP 67 Protection class III Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 55 2000 Hz Housing materials stainless steel 316L 1 4404 stainless steel 304 1 430...