
42
10.6.5 Measured value damping
►
Select [dAP�F] for flow rate measurement or [dAP�P] for pressure
measurement and set damping constant in seconds (τ value 63 %).
Menu CFG:
[dAP�x]
10.6.6 Output logic
►
Select [P-n] and set PnP or nPn�
Menu CFG:
[P-n]
10.6.7 Medium for SDx6xx units
►
Select [MEdi] and set the requested medium: Ar (argon), CO2 (carbon
dioxide), N2 (nitrogen), AIR (compressed air)
�
This parameter cannot be selected for the SDx5xx units�
Menu CFG:
[MEdi]
10.6.8 Low flow cut-off
►
Select [LFC] and set limit, below which a current is evaluated as
standstill�
Menu CFG:
[LFC]
10.6.9 Standard conditions
►
Select [rEF�P] and set the standard pressure�
►
Select [rEF�T] and set the standard temperature�
Menu CFG:
[rEF�P]
[rEF�T]
10.6.10 Zero-point calibration pressure
►
Select [coF] and set value in bar�
> The internal measured value "0" is shifted by this value�
Menu CFG:
[coF]