19
UK
9.2.2 Limit value monitoring with OUT1 / window function
►
Select [SEL1] and set [FLOW]�
►
Select [ou1] and set the switching function:
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
►
Select [FH1] and set the value at which the output switches�
►
Select [FL1] and set the value at which the output is reset�
Menu CFG:
[SEL1]
[ou1]
Main menu:
[FH1]
[FL1]
9.2.3 Configure the analogue output for volumetric flow
►
Select [SEL2] and set [FLOW]�
Menu CFG:
[SEL2]
9.3 Settings for temperature monitoring
9.3.1 Limit value monitoring with OUT1 / hysteresis function
►
Select [SEL1] and set [TEMP]�
►
Select [ou1] and set the switching function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
►
Select [SP1] and set the value at which the output is set�
►
Select [rP1] and set the value at which the output is reset�
Menu CFG:
[SEL1]
[ou1]
Main menu:
[SP1]
[rP1]
9.3.2 Limit value monitoring with OUT1 / window function
►
Select [SEL1] and set [TEMP]�
►
Select [ou1] and set the switching function:
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
►
Select [FH1] and set the value at which the output switches�
►
Select [FL1] and set the value at which the output is reset�
Menu CFG:
[SEL1]
[ou1]
Main menu:
[FH1]
[FL1]
9.3.3 Configure the analogue output for temperature
►
Select [SEL2] and set [TEMP]�
Menu CFG:
[SEL2]