Select [coLr] and define the colour of the characters in the process value
display:
• rEd: red
• GrEn: green
• rxou: colour change from green to red
• Gxou: colour change from red to green
11.4.3 Output logic
u
Select the CFG menu.
u
Select [P-n] and set PnP or nPn.
11.4.4 Measured value damping
u
Select the CFG menu.
u
Select [dAP] and set the damping constant in seconds (τ value 63 %).
11.4.5 Switch-on /switch-off delay
u
Select the CFG menu.
u
Select [dSx] and set the delay for switching OUTx in seconds.
u
Select [drx] and set the delay for resetting OUTx in seconds.
11.4.6 Error behaviour of the outputs
u
Select the CFG menu.
u
Select [FOUx] and set the error behaviour for OUTx:
• Switching output
– On: Output switches ON in case of a fault.
– OFF: Output switches OFF in case of a fault.
– OU: Output switches irrespective of the error as defined with the
parameters.
• Analogue output
– On: The analogue signal goes to 22 mA.
– OFF: The analogue signal goes to 3.5 mA.
– OU: The analogue signal still corresponds to the measured value.