11.3 Setting the output functions
The parameters for flow monitoring and temperature monitoring are set in
the same way. The prerequisite is that the process value for OUT2 has first
been defined via [SEL2] (
30).
11.3.1 Limit monitoring OUTx / hysteresis function
u
Select the CFG menu.
u
Select [oux] and set the switching signal:
• Hno: hysteresis function / normally open
• Hnc: hysteresis function / normally closed
u
Select the main menu.
u
Select [SPx] and set the measured value at which the output switches.
u
Select [rPx] and set the measured value at which the output switches off.
11.3.2 Limit monitoring OUTx / window function
u
Select the CFG menu.
u
Select [oux] and set the switching signal:
• Fno: window function / normally open
• Fnc: window function / normally closed
u
Select the main menu.
u
Select [FHx] and set the upper limit of the window section.
u
Select [FLx] and set the lower limit of the window section.
11.3.3 Frequency signal OUTx
u
Select the CFG menu.
u
Select [oux] and set FRQ.
u
Select the main menu.
u
Select [FSP2] and set the lower temperature value at which 0 Hz is provided.
FSP2 is only available for temperature measurement at OUT2.
u
Select [FEPx] and set the upper measurement value at which the maximum
frequency is provided.