9.2 Define operating mode (optional)
►
Select [CMPT] and set the required operating mode
-[1] = operating mode 1
-[2] = operating mode 2
-[3] = operating mode 3
Description of the operating modes, see
If IO-Link is used, an IODD that corresponds with the operating
mode must be used�
If the operating mode is changed, all parameters will be reset to
factory settings�
9.3 Configure display (optional)
►
Select [Uni] and set the unit of measurement:
-[bAr], [mbAr],
-[MPA], [kPA],
-[PSI],
-[inHG]
The selectable units of measurement depend on the respective unit�
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[rd1], [rd2], [rd3]: display as with d1, d2, d3; rotated by 180°�
-[OFF] = The measured value display is deactivated in the Run mode�
The LEDs remain active even if the display is deactivated�
Error messages are displayed even if the display is deactivated�
Even with unsteady pressure characteristics, [d1] provides optimum
readability; corresponding algorithms are stored�