Select [ou2] and set the switching function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
-[I] = current signal 4���20 mA
-[U] = voltage signal 0���10 V
-[OFF] = output off
Parameter [OFF] is only available in operating mode 3
([CMPT] = [3])
9.4.2 Define switching limits for the hysteresis function
►
[ou1] / [ou2] must be set as [Hno] or [Hnc]�
►
Select [SPx] and set the value at which the output switches�
►
Select [rPx] and set the value at which the output switches off�
rPx is always smaller than SPx� The unit only accepts values which are lower
than the value for SPx�
9.4.3 Define switching limits for the window function
►
[ou1] / [ou2] must be set as [Fno] or [Fnc]�
►
Select [FHx] and set the upper limit�
►
Select [FLx] and set the lower limit�
FLx is always lower than FHx� The unit only accepts values which are lower
than the value for FHx�
9.4.4 Scale analogue value
►
Select [ASP2] and set the value at which 4 mA / 0 V is provided�
►
Select [AEP] and set the value at which 20 mA / 10 V is provided�
Minimum distance between ASP2 and AEP2 = 20 % of the measuring
span (scaling factor 5)�