9.2 Define operating mode (optional)
►
Select [CMPT] and set the operating mode
-[2] = operating mode 2
-[3] = operating mode 3
Description of the operating modes see
When using IO-Link, an IODD suitable for the operating mode must
be used�
When the operating mode is changed, all parameters are reset to
factory setting�
9.3 Configure display (optional)
►
Select [uni] and set the unit of measurement:
-[bAr],
-[MPA],
-[PSI]
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[rd1], [rd2], [rd3]: display as with d1, d2, d3; rotated by 180°�
-[OFF ] = the display is switched off in the operating mode� When one of
the buttons is pressed, the current measured value is displayed for 30 s�
The LEDs remain active even if the display is deactivated�
Error messages are displayed even if the display is deactivated�
Even with unsteady pressure characteristics [d1] provides optimum
readability; corresponding algorithms are stored�
9.4 Set output signals
9.4.1 Set output functions
►
Select [ou1] and set the switching function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
-[OFF] = output off
Parameter [OFF] is only available in operating mode 3
([CMPT] = [3])