O1D110

Photoelectric distance sensor

20

w

[WAIT] is displayed while the repeatability [rEPr] is calculated.

w

The sampling rate [rATE] and repeatability [rEPr] are displayed alternately.

10.3.2 Setting of the repeatability

u

Select [TEAC] and keep [SET] pressed until [WAIT] is displayed.

w

[rATE] and [rEPr] are displayed alternately.

u

If [rEPr] is displayed: Press [SET] until the preset repeatability value flashes.

u

Enter a value incrementally by pressing [SET] repeatedly.

u

Confirm with [MODE/ENTER].

w

[WAIT] is displayed while the sampling rate [rATE] is calculated.

w

The sampling rate [rATE] and repeatability [rEPr] are displayed alternately.

10.4 Extended functions

10.4.1 Set the delay time for switching outputs

u

Select [EF].

u

Press [SET] to change to the menu [EF].

u

Select parameter with [MODE/ENTER]:

u

[dSx] = switch-on delay; [drx] = switch-off delay

u

Set the parameter value with [SET]:

u

Setting range [s]: 0 / 0.1...5 s in steps of 0.1 s\(0 = delay time is not active)

u

Confirm with [MODE/ENTER].

10.4.2 Setting of the fault suppression time for switching output / analogue
output

u

Select [EF].

u

Press [SET] to change to the menu [EF].

u

Select[dFo] (old designation: [dAP]).

u

Set the parameter value with [SET]: Setting range [s]: 0.0...0.1...0.2...0.5...1...2...5.

u

Confirm with [MODE/ENTER].

With [dFo], the error types "too much light" and "not enough light" are suppressed. (

Ò

 Error

indications 

/

 22)

10.4.3 Reset all parameters to factory setting

u

Select [EF].

u

Press [SET] to change to the menu [EF].

u

Select [rES] and keep [SET] pressed until [----] is displayed.

u

Confirm with [MODE/ENTER].

w

The unit changes to the Run mode.

Содержание O1D110

Страница 1: ...Operating instructions Photoelectric distance sensor O1D110 11418505 00 09 2021 GB...

Страница 2: ...10 1 3 Electronic lock 14 10 2 Configuration of the basic settings 15 10 2 1 Selection of the display unit 15 10 2 2 Set the display 15 10 2 3 Configure OUT1 15 10 2 4 Hysteresis function 15 10 2 5 Se...

Страница 3: ...Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Warn...

Страница 4: ...he operating instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for any consequences caused by...

Страница 5: ...Photoelectric distance sensor O1D110 5 Product label...

Страница 6: ...a photoelectric distance sensor 3 1 Applications The photoelectric distance sensor measures distances between 0 2 to 10 m It has a background suppression at 10 to 100 m The measured value is shown in...

Страница 7: ...nput signal at pin 5 Laser Low not used on High Off 4 5 IO Link IO Link is an internationally standardised IO technology IEC 61131 9 for communicating with sensors and actuators General information ab...

Страница 8: ...sured values can be ambiguous 5 2 Mounting accessories The unit is supplied without mounting accessories Examples of mounting accessories Art no Protective cover O1D E21133 Mounting set E2D101 E20938...

Страница 9: ...nk master port class A type A For operation with IO Link master port class B type B observe the following As a standard the unit is not compatible with master port class B type B Pin 2 OU2 and pin 5 I...

Страница 10: ...hing status Is on if the corresponding output is switched 3 4 digit alphanumeric display Indication of the measured distance the parameters and parameter values 4 Programming button SET Setting of the...

Страница 11: ...sis function changes its switching state object near er farther than distance set SP1 is only active if OU1 Hno or Hnc Setting of the switch point for hysteresis function OUT1 16 nSP1 FSP1 Switch poin...

Страница 12: ...rate or repeatability Teach mode 19 EF Extended functions Press SET to open the submenu Extended functions Extended functions 20 dS1 dr1 dS2 dr2 Delay for the switching outputs dSx switch on delay dr...

Страница 13: ...u Briefly press MODE ENTER w The unit goes to the display mode Internally it remains in the operating mode The set parameter values can be read u To scroll through the parameters briefly press MODE EN...

Страница 14: ...lue Then the cycle starts again at the minimum set ting value 3 Confirmation of the parameter value u Briefly press MODE ENTER w The parameter is displayed again the new parameter value is effective 4...

Страница 15: ...effect on the outputs OFF the measured value display is deactivated in the Run mode When one button is pressed the current measured value is displayed for 15 s u Confirm with MODE ENTER The LEDs remai...

Страница 16: ...off when the object approaches When the object is removed again the output switches Switching state of the outputs Output function Object distance D switching status Hno D SPx Closed D SPx Open Hnc D...

Страница 17: ...o Switching state of the outputs Output function Object distance D switching status Fno D nSPx Open D FSPx nSPx D FSPx Closed Fnc D nSPx Closed D FSPx nSPx D FSPx Open Both window limits nSPx and FSPx...

Страница 18: ...lect nSP2 and set the switch point near u Confirm with MODE ENTER u Select FSP2 nd set the switch point far u Confirm with MODE ENTER Window function 16 10 2 11 Scaling of the measuring range analogue...

Страница 19: ...ctory setting Measuring range scaled MEW Final value of the measuring range In the set measuring range the output signal is between 0 and 10 V 10 3 Teach mode 10 3 1 Setting of the sampling rate The s...

Страница 20: ...time for switching outputs u Select EF u Press SET to change to the menu EF u Select parameter with MODE ENTER u dSx switch on delay drx switch off delay u Set the parameter value with SET u Setting r...

Страница 21: ...ensor O1D110 21 10 4 4 Display of the software version number u Select EF u Press SET to change to the menu EF u Select SW then press SET w The software version number is displayed u Press MODE ENTER...

Страница 22: ...N 3 5 mA 0 V 20 5 mA 10 V NoData OL not enough light no ob ject OFF ON OFF ON 20 5 mA 10 V 3 5 mA 0 V NoData UL nEAr object to be measured outside the measuring range 0 2 m ON OFF OFF ON 3 5 mA 0 V 20...

Страница 23: ...sensor free from soiling u For cleaning do not use any solvents or cleaning agents which could damage the plastic parts u After use dispose of the unit in an environmentally friendly way in accordanc...

Отзывы: