mobileIoT gateway
CR3145
7
4.3.1 Cloud logging mode
In cloud logging mode, selected CAN messages are sent to the cloud, processed and stored. In this
case, the unit operates autonomously and does not have to be actively controlled by an application.
The configurations for this mode are made in the
mobile
IoT suite, which can send the data in CAN
messages. An OTA (over-the-air) configuration of the units is carried out via the
mobile
IoT suite.
4.4 Input/output functions
The unit has additional input/output functions (3 analogue inputs, 1 digital output). For example, the
input function can be used to collect device or machine status information or to directly detect and
monitor switch states. The data determined via the input/output functions can be visualised or
transferred via the CAN bus.
The input/output functions are accessed via the following objects:
Object
Index
Subindex
Type
Default
Description
Analogue input 1
0x546F
0x14
R32
ro
—
Pin 4 of the 14-pin Micro Timer II connector
Raw value of the analogue input measure-
ment (Volt)
No filtering applied
Analogue input 2
0x546F
0x15
R32
ro
—
Pin 5 of the 14-pin Micro Timer II connector
Raw value of the analogue input measure-
ment (Volt)
No filtering applied
Analogue input 3
0x546F
0x16
R32
ro
—
Pin 6 of the 14-pin Micro Timer II connector
Raw value of the analogue input measure-
ment (Volt)
No filtering applied
IO – clamp 30
voltage
0x3333
0x67
R32
ro
—
Terminal 30
Raw value of the analogue input measure-
ment (Volt)
IO – clamp 15
voltage
0x3333
0x66
R32
ro
—
Terminal 15
Raw value of the analogue input measure-
ment (Volt)
IO – clamp 15
(ignition) state
0x3333
0x01
U8
ro
—
Terminal 15
0 = input signal low (< 2.5 V)
1 = input signal high (> 5.5 V)
IO = digital out-
put
0x3333
0x0F
U8
rw
—
Pin 7 of the 14-pin Micro Timer II connector
Bit 0: (0 = output signal low, 1 = output sig-
nal high)
Bits 1...7: reserved, set to 0
IO – digital out-
put status
0x3333
0x10
U8
ro
—
Pin 7 of the 14-pin Micro Timer II connector
Bit 0: (0 = output signal error, 1 = output sig-
nal OK)
Bits 1...7: reserved, set to 0
IO – device tem-
perature
0x3333
0x0E
S16
ro
—
Device temperature in °C
The unit can send this data via the CAN interface. The configuration is made via the following objects: