Cylinder sensor with IO-Link

MK59xx

21

- or –

u

Select [Parameter] > [SSC1.x].

u

[SSC1.x Config. ]Select [Mode] and set [Deactivated].

9.8 Diagnostics

The device provides the following diagnostic information via the IO-Link interface:

Operating hours counter (

Ò

 

/

 24)

Power cycles (

Ò

 

/

 24)

Internal temperature (

Ò

 

/

 24)

Stroke time monitoring (

Ò

 

/

 21)

Switching cycle monitoring (

Ò

 

/

 23)

Magnetic field monitoring (

Ò

 

/

 24)

In addition, diagnostic messages can be output as switching signals via the hardware outputs OUT1
and OUT2. The switching output set for the diagnostic message is switched on in normal operation
(normally closed). If the device detects a diagnostic case, the output will be switched off. The switch
point logic cannot be changed.

Diagnostic cases are:

Timeout 1 → 2

 (

Ò

 Stroke time monitoring 

/

 21)

:

The tolerated time window between the activation of SSC1.1 and the activation of SSC1.2 has
been exceeded or not reached.

Timeout 2 → 1

 (

Ò

 Stroke time monitoring 

/

 21)

The tolerated time window between the activation of SSC1.2 and the activation of SSC1.1 was
exceeded or not reached.

Overflow SCT1.1

 (

Ò

 Switching cycle monitoring 

/

 23)

:

The threshold value for the switching cycles counter SCT1.1 has been reached.

Overflow SCT1.2

 (

Ò

 Switching cycle monitoring 

/

 23)

The threshold value for the switching cycles counter SCT1.2 has been reached.

NoData

 (

Ò

 Magnetic field monitoring 

/

 24)

The magnetic field is too strong or too weak or the magnet is outside the measuring range.

9.8.1 Stroke time monitoring

The stroke time monitoring function monitors the time required by the lifting cylinder to change
between two end positions. The two positions (end position 1 and end position 2) are each signalled
by a switching signal via the switching signal channels SSC1.1 and SSC1.2. 
If more or less time is needed for the position change than set via a tolerance time, the "Timeout"
event will be activated.

Stroke time monitoring can be used, for example, to detect wear on the cylinder, dirt in the application
or low air pressure.

9.8.1.1 Stroke time monitoring parameter setting

The time for changing a piston rod between two end positions can be monitored in both directions of
movement of the lifting cylinder. For this purpose, the sequence of the switching process must be
observed when selecting the parameters:

1 --> 2 : Time between deactivation of SSC1.1 and activation of SSC1.2
2 --> 1 : Time between deactivation of SSC1.2 and activation of SSC1.1

Содержание MK59 Series

Страница 1: ...Operating instructions Cylinder sensor with IO Link MK59xx 11463922 00 12 2022 GB...

Страница 2: ...5 9 1 Setting switch points 15 9 2 Teach functions 16 9 2 1 Switch point teach 16 9 2 2 Section Teach 17 9 2 3 Teach In Application 18 9 3 Switch point logic 19 9 4 Switching delay 19 9 5 Signal direc...

Страница 3: ...cessories and further information using the QR code on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross r...

Страница 4: ...architect of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental co...

Страница 5: ...sensor with IO Link MK59xx 5 3 Items supplied Cylinder sensor Cable clip Rubber placeholder The following are additionally required for installation hexagon socket 1 5 mm or slotted screwdriver not i...

Страница 6: ...al aluminium brass or stainless steel Special adapters for mounting on the following cylinder profiles are available as accessories Clean line and tie rod cylinders Integrated profile cylinder Trapezo...

Страница 7: ...omagnetic materials iron permanent magnets and magnetic fields in the vicinity of the device or the encoder magnet can influence and falsify the signal 5 2 Signal range The device provides a measured...

Страница 8: ...between the following switch point modes according to the IO Link smart sensor profile Function Class Object Detection Deactivated Single Point Window Two Point Deactivated If the Deactivated mode is...

Страница 9: ...d can be used to shut down a device or valve prematurely so that the cylinder moves more smoothly into the end stop Cylinder shortly before the end position e g at 80 of the end position LED 1 is on T...

Страница 10: ...tion Thanks to accurate position detection process deviations can be monitored such as the drift of an operation as well as wear and soiling In this way quality monitoring can be carried out independe...

Страница 11: ...scriptions of the device at documentation ifm com IO Link offers the following advantages Interference free transmission of all data and process values Parameter setting in the running process or pres...

Страница 12: ...er towards the end position w LED2 goes on when the switch point SSC1 2 SP1 is reached When both LEDs are on this indicates the middle of the switching area 2 u Fix the device in this position using t...

Страница 13: ...pply according to SELV PELV u Disconnect power u Connect the unit as follows L 1 BN 2 WH 4 BK 3 BU OUT1 IO Link OUT2 L 4 3 2 1 Fig 5 Wiring diagram colours to DIN EN 60947 5 2 BK black BN brown BU blu...

Страница 14: ...of the switching signal channel If the switching signal channel is set to the switch point logic High active the LED goes on when the output is closed If the switching signal channel is set to the swi...

Страница 15: ...evice to a free port of the IO Link master w The unit switches to IO Link mode u Change parameter settings in the software u Write parameter settings to the unit Notes on parameter setting Manual of t...

Страница 16: ...der is fully in the end position SP1 current measured value hysteresis In the Window mode and in the Two Point mode the switch point SPx is set exactly to the current measured value SP1 current measur...

Страница 17: ...x are taught using the current magnet position in an end position and the switch point mode is automatically set to Window The switch points SP1 and SP2 are calculated with the current measured value...

Страница 18: ...least twice the value of hysteresis SSC1 1 and hysteresis SSC1 2 apart PDVmax PDVmin 2x SSC1 1 Config Hyst 2x SSC1 2 Config Hyst Parameter setting 1x 2x 1x 2x 3x PDV 0 4000 Min Max 3x Fig 7 Example al...

Страница 19: ...switch point logic for the switching signal channel SSC1 x 9 4 Switching delay For both switching signal channels a separate delay time can be set for the output to switch and to be reset A switching...

Страница 20: ...re a Teach In Application the assignment of the LEDs can also be changed Parameter setting u Select Parameter Signal Signal direction to set the signal direction 9 6 Output polarity of the switching o...

Страница 21: ...hreshold value for the switching cycles counter SCT1 1 has been reached Overflow SCT1 2 Switching cycle monitoring 23 The threshold value for the switching cycles counter SCT1 2 has been reached NoDat...

Страница 22: ...e setting range will be automatically corrected to the minimum or maximum value during application teach Manual parameter setting u Parameter setting of switching signal channels SSC1 1 and SSC1 2 Det...

Страница 23: ...le threshold is reached The switching status remains active for the set hold time SSC EnhCrt_HoldTime SSC1 x Afterwards the switching output and the counter are reset The counter starts again at 0 SSC...

Страница 24: ...rength Parameter Signal 9 8 3 1 Configuring magnetic field monitoring u Call up Parameters Output Configuration u Select oux and set the diagnostic function for output OUTx dOU diagnostic output u dFU...

Страница 25: ...ion 1 SSC1 2 indicates that the cylinder is in end position 2 In this example the south pole of the magnet is oriented towards the cylinder rod therefore the signal falls when the cylinder is extended...

Страница 26: ...ter set and write it to the device u Retract the cylinder to end position 1 u Select Parameter Teach Teach Single Value u Select TI Select and set SSC1 2 u Save the parameter set and write it to the d...

Страница 27: ...ct SSC1 1 Config Logic and set High active u Save the parameter set and write it to the device u Select SSC1 2 Config Mode and set Window u Set the same switch points as for switching signal channel S...

Страница 28: ...and write it to the device u Retract the cylinder completely u Select SSC1 2 Config Mode and set Window u Calculate and set the switch points for switching signal channel SSC1 2 SSC1 2 Param SP1 3000...

Страница 29: ...nit This includes Product name Product family Manufacturer Manufacturer ID Device ID Serial number Hardware firmware revision Description In addition further freely definable tags with a maximum lengt...

Страница 30: ...n After power on and the required parameter setting the device is in the operating mode It carries out its measurement and evaluation functions and generates output signals according to the set parame...

Страница 31: ...switch point teach has been carried out When the cylinder returns to the end po sition the device will not switch With the switch point teach the switch point is shifted by the hysteresis to the teac...

Страница 32: ...to repair the unit u In case of return shipment ensure that the unit is free from soiling especially from dangerous and toxic substances u For transport only use appropriate packaging to avoid damage...

Страница 33: ...SSC1 1 Diagnostic output dFU1 3 Overflow SCT1 1 Output configuration ou2 2 SSC1 2 Diagnostic output dFU2 3 2 Overflow SCT1 2 SSC EnhCtr_AutoReload SSC1 x OFF SSC EnhCtr_HoldTime SSC1 x 10000 ms SSC En...

Отзывы: