25
UK
Timeout
: If no button is pressed for 30 s during programming, the unit returns to the
operating mode with unchanged values (exception: cOP).
Locking / unlocking:
The unit can be locked electronically to prevent unauthorised setting
(factory setting: not locked).
►
Make sure that the unit is in the normal operating mode.
To lock the unit:
►
Press both buttons simultaneously for 10 s.
> [Loc] is displayed.
For unlocking:
►
Press both buttons simultaneously for 10 s.
> [uLoc] is displayed.
The unit can be configured before or after installation.
Exemption: To adjust the overflow prevention [cOP], the unit must be
installed in the tank.
10.2 Basic settings
Setting ranges of all parameters:
Factory settings of all parameters:
10.2.1 Assign process values to the outputs [SEL3] / [SEL4]
Outputs OUT1 and OUT2: assigned to the process value level.
Outputs OUT3 and OUT4: programmable.
►
Select [SEL3] / [SEL4]
►
Assign process value to the output OUT3 / OUT4:
SEL3
SEL4
[LEVL] = The process value level is assigned to the output.
[TEMP] = The process value temperature is assigned to the output.
10.2.2 Assign process value to the display [SELd]
►
Select [SELd]
►
Select process value that is to be displayed:
SELd
[LEVL] = The process value level is displayed.
[TEMP] = The process value temperature is displayed.