6
4.2 Restriction of the application area
• The unit is not suitable for:
-acids and alkalis,
-hygienic and electroplating applications,
-highly conductive and adhesive media (e�g� glue, shampoo),
-granulates and bulk material,
-use in grinders (increased risk of formation of deposits)�
• It is possible that foam of good conductivity is detected as level:
►
Check proper function by an application test�
• For water-based media with temperatures > 35 °C install the unit in a climatic
tube (accessories)�
►
Check proper function by an application test�
When used as overflow prevention according to the German Federal
Water Act (WHG), no climatic tube must be used�
5 Getting started
For fast set-up, the example configuration described in the following can be used
for most applications� The indicated minimum distances apply exclusively to the
described case�