11.3 Setting the output signals for OUT1
Output OUT-OP (overflow prevention) is fixed to NC [Hnc] for safety
reasons� The principle of normally closed operation ensures that wire
break or cable break is also detected�
11.3.1 Setting the output function [ou1]
►
Select [ou1] and set the switching function:
ou1
[Hno] = Hysteresis function / normally open
[Hnc] = Hysteresis function / normally closed
[Fno] = Window function / normally open
[Fnc] = Window function / normally closed
11.3.2 Define switching limits [SP1] / [rp1] (hysteresis function)
►
Make sure that for [ou1] the function [Hno] or [Hnc] is set�
►
First set [SP1], then [rP1]�
►
Select [SP1] and set the value at which output OUT1 switches�
SP1
►
Select [rP1] and set the value at which the output switches off�
rP1
[rP1] is always lower than [SP1]� The unit only accepts values which are lower than the value
for [SP1]� If [SP1] is shifted, [rP1] also shifts provided that the lower end of the setting range
is not reached�
11.3.3 Define switching limits [FH1] / [FL1] (window function)
►
Make sure that for [ou1] the function [Fno] or [Fnc] is set�
►
First set [FH1], then [FL1]�
►
Select [FH1] and set the upper limit of the acceptable range�
FH1
►
Select [FL1] and set the lower limit of the acceptable range�
FL1
[FL1] is always lower than [FH1]� The unit only accepts values which are lower than the
value for [FH1]� If [FH1] is shifted, [FL1] also shifts provided that the lower end of the setting
range is not reached�
11.3.4 Set switch-on delay [dS1]
►
Select [dS1] and set the value between 0�0 and 60 s�
In accordance with VDMA, the switch-on delay has an effect on [SP1]� The
setting for [ou1] has no significance�
dS1