background image

6

5  Installation

5.1  Typical measuring system

1:  Connection of the return pipe

2:  Pipe adapter with unit

3:  Consumer

4:  Pump

5:  Connection of the rinse pipe

6:  Unit directly screwed into the tank wall

Содержание LDH100

Страница 1: ...Installation Instructions Oil humidity sensor LDH100 706104 01 09 2019 UK...

Страница 2: ...Processing of the measured signals 6 5 Installation 7 5 1 Typical measuring system 7 5 2 Installation location environment 8 5 3 Installation procedure 10 6 Electrical connection 11 7 Operation 12 7 1...

Страница 3: ...ice life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features Only...

Страница 4: ...es the oil temperature by means of a platinum measuring resistor Pt1000 Since the sensor is located directly in the oil the conductivity of the surrounding medium must not exceed a value of 3 ms m Too...

Страница 5: ...ing the formula below w x w max 100 The saturation limit w max depends first of all on the type of oil For further information about the type of oil please contact the manufacturer of the oil Secondly...

Страница 6: ...6 5 Installation 5 1 Typical measuring system 1 Connection of the return pipe 2 Pipe adapter with unit 3 Consumer 4 Pump 5 Connection of the rinse pipe 6 Unit directly screwed into the tank wall...

Страница 7: ...nstalled in a return pipe or a rinse pipe make sure that the pipe does not run dry in any operating situation If the oil in the tank is not sufficiently mixed it is possible that free water settles on...

Страница 8: ...ong installation position 2 Minimum oil level in the tank 3 Connection of the return pipe 4 Connection of the rinse pipe 5 Sensor vertically installed in the bottom 6 Horizontally installed sensor 7 I...

Страница 9: ...of unevenness and dirt Max roughness value Rmax 16 Check profile sealing ring A for correct position in a groove Screw the unit into the G process connection B and tighten firmly Max tightening torque...

Страница 10: ...equipment must be adhered to Voltage supply to EN50178 SELV PELV VDE0100 410 A1 Use a screened sensor cable Disconnect power Connect the unit as follows 6 2 1 4 5 7 3 8 screen L L Out 1 Out 2 1 8 7 6...

Страница 11: ...ity approx 20 70 oil temperature approx 45 C r h relative humidity 8 Maintenance repair disposal From time to time check the sensor for build up and damage If there are any deposits carefully clean it...

Отзывы: