UK
Operating instructions FX460
29
BATCH / TOTAL SET VALUE
A set/reset command (SET BATCH / TOTAL command, via control input) sets the batch counter / total
counter to the value set here� Parameter only visible if BATCH / TOTAL MODE parameter is activated�
0
Lowest value (reset)
…
99999999
Highest value
ROUND LOOP VALUE
This parameter defines the number of steps regarding a round loop function request�
Only for counter configuration A SINGLE or A/B 90 xX
0
Normal display, round loop deactivated
…
99999999
Number of steps for round loop function
9.7 Velocity mode
In this menu, the speed indication from an operating time measurement is defined�
Input A serves as start input and input B as stop input� This menu is only displayed
if the corresponding OPERATIONAL MODE is selected in the GENERAL MENU�
START / STOP
Set the start/stop function�
RISE TO RISE
Start: rising edge on input A
Stop: rising edge on input B
FALL TO FALL
Start: falling edge on input A
Stop: falling edge on input B
RISE TO FALL
Start: rising edge on input A
Stop: falling edge on input B
FALL TO RISE
Start: falling edge on input A
Stop: rising edge on input B
DISPLAY VALUE
Setting of the required value that is to be displayed with the following reference runtime�
1
Lowest value
1000
Default value
99999999
Highest value
BASE TIME (S)
Setting of the time base (in seconds) for the above display value�
0�001
Lowest value
1
Default value
999�999
Highest value