1 Preliminary note
1.1 Symbols used
►
Instruction
>
Reaction, result
[…] Designation of pushbuttons, buttons or indications
→
Cross-reference
Important note
Non-compliance can result in malfunctions or interference�
2 Safety instructions
•
Please read this document prior to set-up of the unit� Ensure that the product is
suitable for your application without any restrictions�
•
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property can occur�
• Check the compatibility of the product materials (→ chapter 10 Technical data)
with the media to be monitored in all applications�
3 Functions and features
The unit detects the system temperature in installations�
3.1 Application
To ensure long-term stability and high accuracy of the unit during operation,
please note:
•
The probe must be inserted into the measured medium up to the sealing
chamfer�
•
Minimum installation depth of the measuring probe: 25 mm�
•
The following limit values must be observed:
Measuring range
-25 ��� +150 °C
-13 ��� 302 °F
Operating temperature process connection
-32 ��� +170 °C
-25�6 ��� 338 °F
Operating temperature electronics
-25 ��� +70 C
-13 ��� 158 °F
Storage temperature
-40 ��� +85 °C
-40 ��� 185 °F
Operating pressure of the medium
≤ 50 bar
≤ 725 PSI
Number of temperature cycles (135 K / 7 s)
< 3000