34
11.4.5 Setting of switching limits (window function)
►
Make sure that for [oux] the function [Fno] or [Fnc] is set.
►
Select [FH1] and set the upper limit of the acceptable range.
►
Select [FL1] and set the lower limit of the acceptable range.
[FLx] is always lower than [FHx]. The unit only accepts values which are
lower than the value for [FHx].
11.4.6 Set the switching delays for switching outputs
►
Select [dSx] and set the value between 0.0 and 60 s.
At 0.0 (= factory setting) the delay time is not active.
The switch-off delay is only active if hysteresis or window function has been
set as switching function ([ou.] = [H..] or [F..]).
11.4.7 Set the switch-off delay for switching outputs
►
Select [drx] and set the value between 0.0 and 60 s.
At 0.0 (= factory setting) the delay time is not active.
The switch-off delay is only active if hysteresis or window function has been
set as switching function ([ou.] = [H..] or [F..]).
11.4.8 Response of the outputs in case of a fault
►
Select [FOU1] / [FOU2] and set the value:
-[On] = output switches ON in case of a fault.
Analogue output switches to a value > 21 mA in case of a fault.
-[OFF] = switching output switches OFF in case of a fault.
Analogue output switches to a value > 3.6 mA in case of a fault.
Factory setting: [FOU1] and [FOU2] = [OFF].
A hardware fault or too low a signal quantity is considered to be a fault.
Overflow is not considered to be a fault!
11.4.9 Set output logic for the switching outputs
►
Select [P-n] and set [PnP] or [nPn].
11.4.10 Set damping for the switching signal
►
Select [dAP] and set a damping constant T in seconds; setting range
0.0...60.0 s