IO-Link master
23
14.4 Connection of IO Link ports and digital inputs
DI 1...4
IOL1...8
X01
X03
X05
X07
X02
X04
X06
X08
IO-Link 1���8 (X01���X08): IO-Link ports 1���8
DI1���DI4 (X01���X04): inputs 1���4
14.5 Pin connection of the inputs and IO-Link ports
1
3
4
2
5
IO-Link-A ports (X01���X04)
1: 24 V DC (L+)
2: DI
3: GND (L-)
4: C/Q
IO-Link data transmission
channel
5: not connected
1
3
4
2
5
IO-Link B ports (X05���X08)
1: 24 V DC (L+)
2: 24 V DC (U
A
)
3: GND (L-)
4: C/Q
IO-Link data transmission
channel
5: GND (U
A
)
Port class A (type A)
The IO-Link port according to type A is assigned an additional hardwired DI (digital input) at pin 2�
Port class B (type B)
The IO-Link port according to type B has an additional supply voltage via pins 2 and 5� This port is
suitable for connecting devices that have a higher current consumption�
Operating modes
The C/Q cable (pin 4) can be configured independently of the other pins� The IO-Link ports can be
operated in the following operating modes:
– DI (behaves like a digital input supplied via U
S
)
– DO (behaves like a digital output supplied via U
S
)
– IO-Link (IOL sensor supplied via US / IOL actuator supplied via U
S
and U
A
)