DI604A
Compact speed monitor M18
14
8 Parameter setting
Parameter setting can be carried out via the IO-Link interface or via the operating elements on the
unit.
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
Depending on the parameter setting, the parameters available in the menu may change.
8.1 Parameter setting via the IO-Link interface
The following parameters can be checked/set via the IO-Link interface among others:
8.1.1 P-n
Output polarity for the switching outputs:
•
PnP (factory setting)
•
nPn
8.1.2 ou1
Output configuration for OUT1:
•
OFF / output off
•
SSC1.1 (factory setting)
8.1.3 ou2
Output configuration for OUT2:
•
ImP / pulse output (factory setting)
•
OFF / output off
•
SSC1.2
When configured as a pulse output, the output switches according to the damped/undamped
state of the sensor.
By combining ou1 and ou2, two switching functions can be implemented in one unit, e.g.:
- SSC1.1 as NO and SSC1.2 as NC with identical switch points → The two outputs switch
complementary.
- With different switch points, different states can be monitored with only one sensor (e.g. “motor
under load” and “motor blocked”).
8.1.4 SSC1.x Param. SP1
Switch point 1:
•
2.1...24,000 pulses/min; factory setting: 100 pulses/min