2  Safety instructions

A qualified electrician must connect the unit� Observe the national and 

international regulations for the installation of electrical equipment�

3  Functions and features

The inductive compact speed monitor with IO-Link determines the frequency 

[pulses/min] with which the sensor is damped without contact� The device 

compares the measured value with the switching thresholds and switches the 

outputs according to the configuration� The device can be operated in the IO-Link 

mode or in the SIO mode (switching output)�

4  Function diagrams

4.1  Single point mode

Normally open (switch point logic  = 1)

SP1: switch-off point

SP1+hyst: switch-on point

The "open" output status indicates that a set rotational speed has not been 

reached�

Normally closed (switch point logic  =  0)

SP1: switch-on point

SP1+hyst: switch-off point

The "closed" output status indicates that a set rotational speed has not been 

reached�

Содержание DI5029

Страница 1: ...Installation instructions Compact speed monitor M18 DC design IO Link with connector DI5029 DI5030 706454 00 10 2017 UK ...

Страница 2: ...tching function normally closed 7 6 IO Link mode 7 6 1 LED display 8 6 2 Setting parameters via IO Link 8 6 2 1 Setting range and conditions for parameter setting 10 6 2 2 Start up delay 11 6 2 3 Background compensation 11 6 2 4 Teach offset 11 6 2 5 Prescaler 11 6 3 Diagnostics and events 12 7 Installation 13 7 1 Tips on flush and non flush mounting in metal 13 8 Electrical connection 14 8 1 Wiri...

Страница 3: ...r maintenance of the device Read this document before use to familiarise yourself with operating conditions installation and operation Keep this document during the entire duration of use of the device WARNING Adhere to the warning notes and safety instructions 2 Safety instructions 1 1 Symbols and warnings used Instructions Cross reference Information Supplementary note Important note Non complia...

Страница 4: ...sured value with the switching thresholds and switches the outputs according to the configuration The device can be operated in the IO Link mode or in the SIO mode switching output 4 Function diagrams 4 1 Single point mode Normally open switch point logic 1 SP1 switch off point SP1 hyst switch on point The open output status indicates that a set rotational speed has not been reached Normally close...

Страница 5: ...ndow mode Normally open switch point logic 1 SP1 switch on point window SP1 hyst switch off point SP2 switch on point window SP2 hyst switch off point Normally closed switch point logic 0 SP1 switch off point window SP1 hyst switch on point SP2 switch off point window SP2 hyst switch on point ...

Страница 6: ...6 2 3 4 1 1 Power on delay time 2 Start up delay 3 NO 4 NC ...

Страница 7: ...g the start up delay Switched conducting On Rotational speed SP SP switch point Hy hysteresis 6 IO Link mode IO Link allows the configuration of internal parameters such as start up delay and switching behaviour normally closed normally open as well as reading the current measured values Furthermore IO Link protects against signal faults and measured value losses as well as tampering with the devi...

Страница 8: ...pecific Tag Application Specific Tag max 32 bytes default P n Output polarity for the switching outputs PNP NPN default PNP SSC1 Param SP1 Setpoint 1 5 24000 pulses min default 5 pulses min SSC1 Param SP2 Setpoint 2 3 21600 pulses min default 3 pulses min SSC1 Config Logic Setpoint logic State for target detected NO NC default NO SSC1 Config Mode Setpoint mode single point window two point mode de...

Страница 9: ...00 ms steps default 0 ms SSC2 Switch Off delay Switching signal channel 2 Switch Off delay 0 60000 ms 100 ms steps default 0 ms PrSC Prescaler indicates the number of targets to calculate current revolution 1 99 default 1 TI Select Teach selection SSC1 SSC2 default SSC1 Teach SP1 Teach switch point 1 Teach SP2 Teach switch point 2 Teach offset Sets an offset between setpoint and current process da...

Страница 10: ... setting To properly set the device parameters the value line below has to be observed It gives important information about the setting range and the resulting conditions Conditions 5 SP1 24000 3 SP2 21600 Hy 10 2 Hy abs SP2 SP1 10 with SP1 SP2 2 1 min ...

Страница 11: ...e for example Background compensation of the device adjusts the sensing range so that the sensor goes into an undamped state and it can detect the object again During background compensation there must not be any object in the desired detection range 6 2 4 Teach offset This parameter allows setting of an offset between the taught process value and the resulting switching value Example Teach offset...

Страница 12: ... 545 BitCoded_ActiveEvents 35888 d 8C 30 h Process variable range under run Warning Process data uncertain Note This event will not be transmitted via IO Link Event mechanism it is only available by reading index 37 DetailedDeviceStatus or 545 BitCoded_ActiveEvents 36350 d 8D FE h Test Event 1 Warning Event appears by setting index 2 to value 240 Event disappears by setting index 2 to value 241 36...

Страница 13: ...e using a bracket and secure it by means of the nuts provided so that it cannot work loose Adhere to the above mounting specifications to ensure a correct function 7 1 Tips on flush and non flush mounting in metal Installation instructions cylindrical design 2xSn flush non flush ...

Страница 14: ...h non flush Side by side installation only possible with different oscillator frequencies 8 Electrical connection Disconnect power Connect the device according to the wiring diagram 8 1 Wiring L L 1 4 3 L L 1 4 3 DI5029 DI5030 SIO 4 Switching output PNP NPN programmable via IO Link IO Link 4 IO Link communication Factory setting PNP normally open ...

Страница 15: ...monitor 10 Scale drawing EPS Source Product Scale Drawing Frame Size 80 mm x 22 5 mm Original Scale Drawing MTD MZ_100_0701 M18 x1 M12 x1 45 49 60 LED 4 x 90 24 4 M18 x1 M12 x1 45 49 60 LED 4 x 90 24 4 EPS Source Product Scale Drawin Frame Size 80 mm x Original Scale Drawing P_MZ_100_0702 M18 x1 35 10 M12 x1 60 LED 4 x 90 49 24 4 M18 x1 35 10 M12 x1 60 LED 4 x 90 49 24 4 DI5029 DI5030 Dimensions m...