AL4103
Remote I/O module 16 DI
18
Temperature
I
UA-daisy-chain
(XD2)
I
USmax
(XD1)
I
US
(X1…X8)
I
US-daisy-chain
(XD2)
60 °C
8 A
8 A
0 A
8 A
60 °C
1 A
7 A
Explanation: The current I
USmax
at port XD1 is the sum of the currents I
US
taken from ports X1…X8 and
the current I
US-daisy-chain
taken from port XD2 for the supply of further devices.
Formula: I
USmax
(XD1) = I
US
(X1…X8) + I
US-daisy-chain
(XD2)
The less current is consumed at ports X1...X8, the more current will be available to supply further
devices via daisy chain through port XD2.
6.6 Voltage output
An additional device can be supplied via the power OUT port (daisy chain). The supply voltages US
and UA are looped through from port XD1 to port XD2.
Max. current of US: 15.9 A
Max. current of UA: 16 A
u
Optional: Connect an additional device to port XD2.
u
For connection, use an L-coded M12 connector (with at least protection rating: IP65 / IP66 / IP67 /
IP69K).
u
Tighten the cable plug using 1.3 ± 0.1 Nm.
u
Observe the derating behaviour of the device (
Wiring:
2
4
1
3
5
1:
+24 V DC (US)
2:
GND (UA)
3:
GND (US)
4:
+24 V DC (UA)
5:
FE