AL4103
Remote I/O module 16 DI
42
9.3.2.3 Use Isochronous Realtime (IRT)
The unit supports participation in a network with activated IRT protocol.
9.3.3 Configure the device
The device is configured via slot 0, subslot X1. The module [PN-IO] is permanently assigned to the
slot. The assignment cannot be changed.
Requirements:
ü
Device is integrated in PROFINET project.
u
Open the [Device view].
w
The [Device overview] tab displays the device structure.
u
Click on the module [PN_IO] in the slot [0 X1].
w
The [Properties] view appears.
w
The [General] tab displays the available configuration options of the device.
u
Set the parameters.
w
The device has been configured.
9.3.3.1 Use Prioritized Startup
The device supports the Prioritized Startup function.
To activate the Prioritized Startup function:
Requirements:
ü
Device is integrated in PROFINET project.
u
Open the [Device view].
u
Click on the module [PN_IO] (slot 1, subslot X1).
w
The [General] tab displays general configuration options.
u
Select [Advanced options] > [Interface options].
u
Activate the [Prioritized startup] option.
w
The Fast Startup function has been activated.
9.3.3.2 Use Fast Startup
The device supports the Fast Startup function (FSU).
Achieving the guaranteed fast startup time depends on the complexity and elements used in the
PROFINET network.
To activate the Fast Startup function:
Requirements:
ü
Device is integrated in PROFINET project.
ü
The Fast Startup function has been activated.