AL4042
Remote I/O module 16 DI
48
Mapping: Filter Settings
Word
(Offset)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
n
reserved
res.
res.
res.
res.
res.
res.
res.
INV
n+1
reserved
res.
res.
res.
res.
res.
res.
res.
HL
n+2
Debounce Time
n+3
Hold Time
Legend:
• INV
Invert: signal inversion
1 BIT
• 0x0: do not invert (default)
• 0x1: invert
• HL
Hold Level: Signal level to be maintained
1 BIT
• 0x0: LOW
• 0x1: HIGH (default)
• Debounce Time
Debounce time (value in *0.1 milliseconds)
1 WORD • 0x0000: 0 ms (default)
…
• 0x01F4: 50 ms
• Hold Time
Hold time (value in *0.1 milliseconds)
1 WORD • 0x0000: 0 ms (default)
…
• 0xEA60: 600 ms