Remote I/O module 16 DI
AL4042
31
9.2.3 Configuring the device
The [Parameters] menu page provides access to the configuration options of the device.
The configuration created via the IoT Core Visualizer is overwritten when a connection is
established between the device and the ModbusTCP PLC.
Requirements:
ü
IoT Core Visualizer has been launched.
u
Select the [Parameter] menu.
w
The menu page displays the available parameters of the device.
9.2.3.1 Configuring a ModbusTCP interface
Changes to the
byteswap
data point will only take effect after the device has been restarted.
Available parameters:
Name
Description
Value range
Access
[network] > [dhcp]
Status of the DHCP client
• Static IP: Static IP address
• DHCP: DHCP (Dynamic Host
Configuration protocol)
• BOOTP: BOOTP (Bootstrap
Protocol)
rw
1
[network] > [ipaddress]
IP address of the Ethernet interface
e.g. 192.200.0.100
• 192.168.1.250 (default)
rw
1
[network] > [subnetmask]
Subnet mask of the network segment
e.g. 255.255.192.0
• 255.255.255.0 (default)
rw
1
[network] > [ipdefaultgateway] IP address of the network gateway
e.g. 192.200.63.1
• 0.0.0.0 (default)
rw
1
[network] > [macaddress]
MAC address of the Ethernet interface
e.g. 00:02:01:0E:10:7C
ro
2