53
ifm
Device Manual IO-Link Master with Modbus interface CabinetLine 8 Ports IP 20 (AL1940)
05 / 2018
Configuration
Modbus
>
8.3.4
Read input data of individual IO-Link ports
23072
Register area for separate access to input data of the individual IO-Link ports:
→
Single Port Access
(
The area contains the following data for each IO-Link port X01...X08:
Digital input data at clamp 2 / clamp 4 (DI)
Diagnostic and status information of the connected IO-Link devices
Input data IO-Link
Observe the general rules for access to the Modbus registers (
→
Rules for accessing the Modbus
register
(
The parameter "Invalid Data" indicates whether the read IO-Link input data is valid.
► Also read and evaluate the corresponding diagnostic information!
Register area
Contents
Access
Start
address
Length
(words)
1000
1
Port X01: Digital Input - Pin 2 / Pin 4 (DI)
r
1001
1
Port X01: Diagnostic data
r
n/2
Port X01: Input Data - IO-Link (n bytes)
r
2000
1
Port X02: Digital Input - Pin 2 / Pin 4 (DI)
r
2001
1
Port X02: Diagnostic data
r
n/2
Port X02: Input Data - IO-Link (n bytes)
r
3000
1
Port X03: Digital Input - Pin 2 / Pin 4 (DI)
r
3001
1
Port X03: Diagnostic data
r
n/2
Port X03: Input Data - IO-Link (n bytes)
r
4000
1
Port X04: Digital Input - Pin 2 / Pin 4 (DI)
r
4001
1
Port X04: Diagnostic data
r
n/2
Port X04: Input Data - IO-Link (n bytes)
r
5000
1
Port X05: Digital Input - Pin 2 / Pin 4 (DI)
r
5001
1
Port X05: Diagnostic data
r
n/2
Port X05: Input Data IO-Link (n bytes)
r
6000
1
Port X06: Digital Input - Pin 2 / Pin 4 (DI)
r
6001
1
Port X06: Diagnostic data
r
n/2
Port X06: Input Data - IO-Link (n bytes)
r
7000
1
Port X07: Digital Input - Pin 2 / Pin 4 (DI)
r
7001
1
Port X07: Diagnostic data
r
n/2
Port X07: Input Data - IO-Link (n bytes)
r
8000
1
Port X08: Digital Input - Pin 2 / Pin 4 (DI)
r
8001
1
Port X08: Diagnostic data
r
n/2
Port X08: Input Data - IO-Link (n bytes)
r
r .. read only
n = [2,4,8,16,32]; is determined by parameters [Process Data Length] (
→
Configuration Area
(