IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
29
>
9.1.4
IoT: Configure access rights
34046
The access rights define which instance may read and / or write the parameter data, process data and
event/diagnostic messages.
In order to configure the access rights to the IO-Link master:
►
Select [IoT] menu.
>
The menu page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[Access Rights]
The access rights to the
parameter data, process data
and the event/diagnostic
messages of the IO-Link master
as well as the connected IO-Link
devices
[Modbus TCP + IoT]
Modbus TCP and IoT Core have read
and write access rights to parameters
and process data
Modbus TCP and <IoT Core> have
read access rights to events/alarms
[Modbus TCP + IoT
(read-only)]
Modbus TCP has read and write
access rights to parameters and
process data
Modbus TCP has read access rights to
events/alarms
IoT Core only has read access rights to
parameters, process data and
events/alarms
[IoT only]
IoT Core has read and write access
rights to parameters and process data
IoT has read access rights to
events/alarms
Modbus TCP has no access rights
►
Save changed values on the device.
If the parameter [Access rights] is set to [Modbus TCP + IoT] via IoT and Modbus TCP
projection, then the parameter values set in the Modbus TCP projection software apply.
If the parameter [Access rights] is set to [IoT only] via IoT, then set the parameter [Access
rights] to [Keep settings] in the Modbus TCP projection software.
Changes of the parameter [Access Rights] are only effective after restarting the device
(
→
Firmware: Reboot the device
(