IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
39
>
9.2.4
Configure AL1120
34357
The AL1120 is configured via the controller tags.
Requirements:
>
AL1120 is correctly integrated in the EtherNet/IP project (→
Integrate the AL1120 into the EtherNet/IP
project
1 Open controller tags
►
In the Controller Organizer: Double click on [Controller Name_of_Project] > [Controller Tags]
>
[Controller Tags] window appears.
►
In the tree view: Click on [AL1120:C].
>
Controller tags for the configuration of the device appear.
2 Configure AL1120
►
Set the following controller tags as required:
Name
Description
Possible values
[AL1120:C.Communication_Profile]
The access rights to the
parameter data, process data
and events/diagnostic
messages of the IO-Link
master and the connected
IO-Link devices
0x00
EtherNet/IP + LineRecorder
EtherNet/IP and LR DEVICE have read
and write access rights to parameters and
process data
EtherNet/IP and LR DEVICE have read
access rights to events/alarms
0x01
EtherNet/IP + LineRecorder (ro)
EtherNet/IP has read and write access
rights to parameters and process data
EtherNet/IP has read access rights to
events/alarms
LR DEVICE only has read access rights to
parameters, process data and
events/alarms
0x02
EtherNet/IP only
EtherNet/IP has read and write access
rights to parameters and process data
EtherNet/IP has read access rights to
events/alarms
LR DEVICE has no access rights
(parameters, process data, events/alarms,
web interface, firmware update)
0x03
Continue in Use Case
previous setting is valid
[AL1120:C.Port_Process_Data_Size] Length of the process input
data and process output data
0x00
2 bytes input, 2 bytes output
0x01
4 bytes input, 4 bytes output
0x02
8 bytes input, 8 bytes output
0x03
16 bytes input, 16 bytes output
0x04
32 bytes input, 32 bytes output
►
Save EtherNet/IP project