IO-Link Master with AS-Interface Interface StandardLine 2 Ports IP 65 / IP 66 / IP 67
39
>
13.1.4 Inputs
59332
Inputs
Number of digital inputs
4; (IO-Link Ports Class A: 2 x 2)
Sensor supply
AS-i
Switching level high [V]
11...30
Switching level low [V]
0...5
Short-circuit protection of the digital inputs
yes
>
13.1.5 Outputs
59333
Outputs
Number of digital outputs
2; (IO-Link Port Class A: 2 x 1)
Current rating per output [mA]
300
Short-circuit proof
yes
Actuator supply of the switching outputs
AS-i
>
13.1.6 Interfaces
51998
Interfaces
Communication interface
IO-Link; AS-i
IO-Link master
Type of transmission
COM 1 / COM 2 / COM 3
IO-Link revision
V1.1
Number of ports Class A
4
>
13.1.7 Operating conditions
52488
Operating conditions
Ambient temperature [°C]
-25...60
Storage temperature [°C]
-25...85
Max. perm. relative air humidity [%]
90
Protection rating
IP 65; IP 66; IP 67
Pollution Degree
2