SmartPLC DataLine with EtherCAT slave interface
57
>
Change the analogue output values manually
41598
To change the analogue output values of an AS-i slave manually:
1 Enable manual access to the outputs
►
Set [Output access] parameter = Manual (→
Set the output access
2 Select the menu page
►
>
or
>
►
Select an AS-i slave (→
Slave selector
(→ S.
►
Select [Data] tab.
3 Set the analogue output values manually
>
[Outputs] group shows the current value of the analogue output.
►
Change the value of the requested channel one digit at a time (→
Numerical field
(→ S.
>
Selected value is applied.
►
Optional: repeat step 3 to change further channels.
>
Show AS-i slave information
41643
To display information about an AS-i slave:
1 Select the menu page
►
>
or
>
►
Select an AS-i slave (→
Slave selector
(→ S.
►
Select [Information] tab.
2 Display information about the AS-i slave
>
Page shows the following information:
Name
Description
Possible values
[AS-i slave addess]
Current address of the AS-i slave
e.g.
13B
[Slave status]
Current status of the AS-i slave
AS-i slave is active
AS-i slave is missing
Not projected
Double address error
Periphery fault
[AS-i slave profile]
Current (= Current) and expected
(= Preset) slave profile (IO, ID, ID2,
ID1) in hexadecimal format
►
Use [
] / [
] for page navigation.