SmartPLC DataLine with Profinet device interface 
 

71 

 

Set the system time 

41412 

The system time consists of date and time. The device provides the following options for setting the 
system time: 

 

Manual: 

The operator sets the date and time manually.   

 

Via NTP server: 

The device has an NTP client. The system time can be synchronised 
with an NTP server. 

 

Apply the system time of 
a PC/laptop: 

The device adopts the system time of a PC/laptop (only available via 
the web interface of the device) 

  

To set the system time: 

1  Select the menu page 

► 

  > 

 

► 

Select [Clock] tab. 

2  Display the current system time settings 

>

 

The following parameters display the current system time settings: 

Parameter 

Description 

Possible values 

[Activate NTP] 

Activate the NTP client of the 
device 

 

NTP client is deactivated: 
Device adopts the manually set values for [Time] and 
[Date]. 

 

NTP client is not active: 
From an NTP server, the device adopts the values for 
[Time] and [Date]. 

Status LED 

Status of NTP client and 
synchronisation with NTP 
server 

[NTP not active

NTP client is deactivated: 
Applicable are the manually set values 
for [Time] and [Date]. 

[NTP waiting

NTP client is active: 
Device waits for messages from NTP 
server. 

[NTP successful

NTP client is active: 
Time synchronisation with NTP server 
was successful. 

[Time] 

System time 
(format [hh:mm:ss]) 

e.g. 

12:23:56

 

[Date] 

System date 
(format [yyyy-mm-dd]) 

e.g. 

2014-04-23

 

  

3  Select the configuration method 

► 

Select one of the following: 
  – 

Set the system time manually

 (→ S. 

72

) 

  – 

Synchronise the system time with an NTP server

 (→ S. 

73

) 

  – 

Adopt the system time of the PC

 (→ S. 

74

) 

Содержание AC1403

Страница 1: ...7391120 01 09 2018 Device Manual SmartPLC DataLine with Profinet device interface AC1403 AC1404 Master profile M4 Firmware 4 3 1 or higher English...

Страница 2: ...14 4 1 Control of the graphical user interface 14 4 1 1 Function keys 15 4 1 2 Arrow keys 15 4 2 Menu view 16 4 2 1 Menu navigation 16 4 2 2 Navigation aids 17 4 3 Page view 19 4 3 1 Navigate on a pa...

Страница 3: ...1 1 EtherNet IP interface 96 6 1 2 Configuration interface 96 6 2 zzStart screen Basic settings 97 6 2 1 Change the basic settings of the device 97 6 3 Update the firmware of the device 99 6 3 1 Behav...

Страница 4: ...ect connection 115 8 4 2 Connection via Ethernet network 116 8 5 AS i master 117 8 5 1 Operating modes of the AS i master 118 8 5 2 Master flags 120 8 6 AS i slaves 121 8 6 1 Profiles of AS i slaves 1...

Страница 5: ...iceNet Vendor Association USA www odva org EtherNet IP is the property of the ODVA EtherCAT is a registered trade mark and patented technology licensed by Beckhoff Automation GmbH Germany IO Link www...

Страница 6: ...versible injuries may result NOTICE Property damage is to be expected or may result Important note Non compliance can result in malfunction or interference Information Supplementary note Request for a...

Страница 7: ...wing Device manual Notes on operation of the device via GUI and web interface Error elimination Description of the fieldbus data Supplement device manual Description of the acyclic data sets and the c...

Страница 8: ...e device or incorrect use by the operator Observe these operating instructions Adhere to the warning notes on the product 2 2 Required background knowledge 41648 This document is intended for speciali...

Страница 9: ...SmartPLC DataLine with Profinet device interface 9 3 System description Content Intended use 10 Information concerning the device 11 28392...

Страница 10: ...ol the data exchange to the sensor actuator level as gateway between the AS i network and a higher level controller PROFINET Controller Host e g PLC via the fieldbus interface as Programmable Logic Co...

Страница 11: ...view 36757 Legend Display Status LED H1 2 function keys 4 arrow keys Connector X1 for AS i 1 AS i 2 functional earth Connector X2 for AUX here with AUX jumper Front flap Slot for SD card behind the fr...

Страница 12: ...ical data Technical data S 112 Status LEDs 36784 The device features the following status LEDs which display the current status of system components Meaning of the LED colours and flashing frequencies...

Страница 13: ...device communicates with the higher level control instance of the PROFINET network via the PROFINET interface X6 X7 Notes regarding connetion concepts Configuration interfaces Connection concepts S 1...

Страница 14: ...graphical user interface 41568 Below the display is the key panel with six membrane keys The operator controls the graphical user interface of the device with these keys The key panel is closely linke...

Страница 15: ...the function key is pressed in the current work step If the function key is not labelled it means that it has no function in the present situation Example figure The left function key triggers the act...

Страница 16: ...view are the three navigation bars They reflect the menu structure of the device software Each navigation bar represents a menu level The symbols in a navigation bar represent the submenus and menu it...

Страница 17: ...cus Navigation path to the focused menu element Example 41499 To access the menu page containing the setting options for the device internal PLC 1 Initial position when accessing the menu screen 2 Use...

Страница 18: ...interface 18 6 Use to select the Settings menu symbol The focus is on the Settings menu symbol Press the Select function key to go to the page view of the Settings menu item The page shows the settin...

Страница 19: ...elected element is marked orange frame Use the Back function key to return to the tab menu menu view Rules for using the different control elements Description of the control elements S 20 4 3 2 Use n...

Страница 20: ...interface 20 4 3 3 Description of the control elements Content Tab menu Tab 21 Button 22 Checkbox 22 List 23 Slave selector 24 Confirmation message 29 Numerical field 30 Binary field 31 41586 A page...

Страница 21: ...ground colours Tab has the focus Tab is active Tab is inactive Use 1 Select the menu item Go to the menu item with the tab menu The tab menu appears The focus is on the left hand tab 2 Select a tab Us...

Страница 22: ...ed Checkbox 41600 A checkbox permits the user to activate deactivate a parameter A checkbox control element consists of a checkbox and a caption Example Use 1 Select a checkbox Use arrow key to select...

Страница 23: ...in this exampleGateway 2 Activate the list Use Select function key to open the list The opened list shows the selectable values 3 Select a value Use arrow key to select the desired value from the lis...

Страница 24: ...Every field represents an AS i address An AS i address can be occupied by a single slave symbol an A B slave pair symbol The row and column headers help to locate the AS i address Example address of...

Страница 25: ...s Slave active Not projected configuration error Double address double address error Periphery periphery fault Use 1 Select an AS i slave Use the arrow keys and to select the desired AS i slave The fo...

Страница 26: ...nd slave in LDS is not projected in LPS the found slave has another profile than projected Meaning of the colour combinations example configuration error type 2 41741 Symbol Colour Meaning grey red gr...

Страница 27: ...status of the selected AS i slave Possible status messages Free Missing slave Use 1 Select the AS i address Use the arrow keys and to select the desired AS i address The focus orange frame is on the s...

Страница 28: ...e addressed is an A B slave A address is free B address is used grey blue Slave to be addressed is an A B slave A address is used B address is free turquoise turquoise Slave to be addressed is an A B...

Страница 29: ...on Change AS i slave address from 1a to 1b Confirmation message shows Action Change AS i address Slave address prior to change Slave address after change The operator has the following input options S...

Страница 30: ...ot be edited Analogue value Entry of an analogue output value Value range per numerical field 0 9 Use using the example of the numerical date field 1 Select a numerical field Use arrow key to select t...

Страница 31: ...arrow key to select the binary field The focus orange frame is on the selected binary field The control element shows the current value digital and hexadecimal 2 Activate the editing mode Press Selec...

Страница 32: ...thernet based network 4 4 1 General 41475 The operating concept of the web interface follows the same philosophy as the operating concept of the local display The web interface uses the same menu item...

Страница 33: ...mouse touchpad is used instead of the following key functions Navigation functions of the arrow keys Selecting functiions of the function keys Select and Back Example To select Place the cursor on sym...

Страница 34: ...ace Operating instructions S 33 At the top of the web interface the status bar displays the following status message Enter the fixed password in the Password field Click Login to log in to the web int...

Страница 35: ...the web interface containing diagnostic and information data An error message is displayed when a user in the web interface accesses a menu with device settings The user stays logged into the web int...

Страница 36: ...ic settings S 97 The start screen displays the status information of important system components Moreover the graphical user interface is accessed and operated from the start screen AS i Master 1 oper...

Страница 37: ...e interfaces PROFINET Configuration interface Interfaces S 80 Online Support Centre Online Support Center OSC S 108 Control and administration of the ifm system solutions ifm apps ifm system solutions...

Страница 38: ...nfigure the operating mode of the AS i masters S 40 Quick setup Configure the output access S 41 Quick setup Access the device via QR code S 42 Quick setup Configure the PROFINET interface S 42 Quick...

Страница 39: ...ct tab Project all 2 Select the AS i master for projection adaptation Set the following parameters as required Parameter Description Possible values AS i Master 1 Select AS i Master 1 for projection a...

Страница 40: ...tion mode inactive AS i network runs in protected mode normal mode Projection mode active AS i network can be projected Quick setup Address the AS i slaves connected to AS i Master 1 S 45 or Quick set...

Страница 41: ...ation modes tab 2 Set the control instance for the outputs of the AS i slaves From the list Output access select the desired value Parameter Description Possible values Output access Control instance...

Страница 42: ...QR Code tab The display shows the QR code 2 Read the QR code Start the QR code reading app and scan the QR code The smartphone displays the web interface of the device Remote access S 32 5 3 5 Quick s...

Страница 43: ...rs below show the active settings Parameter Description Possible values Optain IP address autom Active method for the configuration of the interface parameters Manual assignment of the interface param...

Страница 44: ...Zeroconf protocol The automatic configuration of the interface takes approx 10 seconds 5 Show the current settings The parameters step 2 show the active IP settings of the Konfigurationsschnittstelle...

Страница 45: ...AS i address The page provides an overview of the free AS i addresses figure Notes on colour codes Overview of free slave addresses S 27 Select the address to be assigned to the AS i slave Assign the...

Страница 46: ...the AS i slaves connected to AS i Master 2 is the same as for addressing the AS i slaves connected to AS i Master 1 Quick setup Address the AS i slaves connected to AS i Master 1 S 45 To change the a...

Страница 47: ...he monitoring functions of the AS i master S 49 AS i network diagnosis Display and reset the error counters S 50 Display the error statistics of the AS i slaves S 50 Display the voltage supply analysi...

Страница 48: ...cted AS i slaves Set the following parameters as required Parameter Description Possible values Projection mode Active operating mode of the AS i master Projection mode inactive AS i network operates...

Страница 49: ...button The projection adaptation is carried out If successful All slaves on the AS i master are projected If not successful The Online Support Center displays an error message Remove the error and re...

Страница 50: ...rred Voltage 22 5V Number of voltage errors 22 5 V Voltage 19 0V Number of voltage errors 19 0 V Earth fault Number of detected earth faults 3 Optional reset the error counters Press Reset button All...

Страница 51: ...C earth fault Evaluation of the network symmetry AS i network is symmetrical AS i network is asymmetrical AS i network has earth fault Graphical representation of the network symmetry Display and rese...

Страница 52: ...Data tab 2 Display input output data Depending on the profile of the selected AS i slave the page displays the following data Digital input 41464 Name Description Example Possible values Inputs Curren...

Страница 53: ...the editing mode Jog mode enabled momentary switch mode The changes immediately affect the output Analogue output 41521 Name Description Example Possible values Outputs Current values of the analogue...

Страница 54: ...tivated After changing the slave outputs the output values remain on the changed values Change the inverted outputs again immediately to the original values after the end of the test To change the dig...

Страница 55: ...me Numerical field S 30 Selected value is applied Optional repeat step 3 to change further channels Show AS i slave information 41643 To display information about an AS i slave 1 Select the menu page...

Страница 56: ...l change further AS i addresses Repeat step 2 to change further AS i slave addresses After the address change the present configuration LDS no longer corresponds to the stored configuration LPS The OS...

Страница 57: ...Setup tab 2 Set the Extended ID1 The ID1 list displays the current Extended ID1 value hexadecimal format Select the desired value for Extended ID1 from the ID1 list Selected value is applied After ch...

Страница 58: ...ow version information S 65 System settings Set the output access S 66 Enable Disable the device internal PLC S 67 Adjust device cycle S 68 Switch the menu language S 69 Set the behaviour of the displ...

Страница 59: ...rmation Display the status of the CODESYS SPS S 60 Display information about SPS projects S 60 SPS settings Control a single SPS application S 61 Control SPS applications S 62 Show target visualisatio...

Страница 60: ...Status LED Status of the device internal SPS The CODESYS SPS is disabled The CODESYS SPS is enabled Version CODESYS version e g 3 5 3 60 Node name Name of device in CODESYS project e g ifm_SmartPLC_Da...

Страница 61: ...ab 2 Select an application Use to select the message field The focus orange frame is on the message field Use to select the requested application Perform one of the following actions Launch a single S...

Страница 62: ...h step 4 Reset all SPS applications continue with step 5 3 Launch all SPS applications Press Starten button The confirmation prompt appears Press OK to confirm the prompt All SPS applications are star...

Страница 63: ...appears after activating the Activate Target Visu button To exit the target visualisation and return to the menu page Press and simultaneously If the device does not react when entering the key combi...

Страница 64: ...me Description CODESYS Memory capacity occupied by CODESYS data in Kbytes free Free memory in Kbytes The current usage of memory space is read out once when calling up the menu page These values are n...

Страница 65: ...information about the hardware and software components of the device 1 Select the menu page Select Version tab 2 Show version information Page shows the following information Name Description Possibl...

Страница 66: ...rs as required Name Description Possible values Output access Control instance of the AS i slave outputs Gateway A higher level PLC controls the outputs of the AS i slaves Manual The operator controls...

Страница 67: ...device internal PLC Control SPS applications S 62 Implement a safe state when programming the PLC applications When activating the device internal PLC PLC applications stored on the device are starte...

Страница 68: ...t master can be interrupted Risk of material damage to the machine plant Select a device cycle between 1 5 to 2 milliseconds If the PLC is disabled the device operates with a fixed cycle time of 0 7 m...

Страница 69: ...h Fran ais French Espa ol Spanish Italiano Italian Portugu s Portuguese 3 Save the changes Press Accept selection button GUI elements are displayed in the requested language Optional switch the langua...

Страница 70: ...required Parameter Description Possible values Screen saver Status of the screen saver Screen saver is inactive Display remains permanently switched on Screen saver is active Display is switched off a...

Страница 71: ...escription Possible values Activate NTP Activate the NTP client of the device NTP client is deactivated Device adopts the manually set values for Time and Date NTP client is not active From an NTP ser...

Страница 72: ...NTP client of the device Uncheck Activate NTP Set the system time S 71 Press Accept selection button The changes become effective NTP status NTP not active 3 Set the system time manually Set Time and...

Страница 73: ...ers as required Parameter Description Possible values IP address field IP address of the NTP server e g 192 168 0 100 NTP Offset optional Time zone of the NTP server in UTC Universal Coordinated Time...

Страница 74: ...n interfaces Connection concepts S 115 Start the web browser and open the web interface of the device Recommended browsers S 32 This function can only be executed via the web interface of the device 1...

Страница 75: ...ce via an SD card A device configuration consists of the following settings System settings AS i 1 AS i 2 settings PROFINET settings SPS applications incl PLC task configuration variables and data Clo...

Страница 76: ...ed with the FAT32 file system SD cards with other file systems are not recognised by the AC1403 04 To allow identification of the saved configuration the export file is saved using the following name...

Страница 77: ...is restored Check before the import if the required device configuration is saved on the SD card identification of the saved device configuration Export device configuration S 76 Save only the device...

Страница 78: ...ge AS i configuration PROFINET configuration System settings CODESYS information OSC history This function is only available via the web interface of the device Remote access S 32 Requirements Connect...

Страница 79: ...f device since last system start LCD Operating time of LCD SPS Operating time of controller Temperatur Current device temperature Indications in C Note Versorgt durch Voltage supply of device Aux Volt...

Страница 80: ...on options of the device s interfaces Navigation path Functions Configuration interface 1 Configure the IP parameters manually S 82 Configure the IP parameters automatically S 82 Show Ethernet informa...

Страница 81: ...arameters of the configuration interface 1 Select the menu page Select IP setup tab 2 Show the active settings The parameters below show the active settings Parameter Meaning Possible values Optain IP...

Страница 82: ...ers automatically 41604 The device must be connected to a DHCP server to automatically receive the interface parameters via DHCP Connect the configuration interface X3 to a DHCP server To configure th...

Страница 83: ...tionsschnittstelle 2 menu provides access to the settings of the Ethernet configuration interface 2 port X2 The Ethernet configuration interfaces 1 X3 and 2 X8 must not be participants of the same Eth...

Страница 84: ...to information settings and diagnostic data regarding the PROFINET interface Navigation path Functions PROFINET information Display I M information S 85 Display PROFINET data S 86 Display module confi...

Страница 85: ...Select menu page Select I M information tab 2 Display I M information Page shows the following information Designation Description Manufacturer ID Manufacturer ID Order number Article no of the device...

Страница 86: ...ngle slave OR 2 channels per A slave 4 channels 4 channels per single slave OR 2 channels per A B slave Analog channels O slave Number of analogue channe3ls per projected output slave Analog channels...

Страница 87: ...ive module configuration of the PROFINET Slots appendix The fieldbus slots can only be configured in the PROFINET projection software Download GSDML file 41501 This function is only available via the...

Страница 88: ...ration on the device In order to PROFINET configure the interface 1 Select menu page 2 Set IP parameters of the PROFINET interface Set the following parameters as required Parameters Description Possi...

Страница 89: ...enu page 2 Display diagnostic data Page shows the following information Name Description Possible values PROFINET connection status Display of the connection status of the PROFINET interfaces Status p...

Страница 90: ...f AC1403 04 Remote access S 32 The ifm system solutions menu provides access to information and installation options for ifm system solutions Navigation path Functions ifm system solutions Show inform...

Страница 91: ...03 04 Enable Disable the device internal PLC S 67 Users can download the available ifm system solutions from ifm s website Types of ifm system solutions 41684 There are 2 types of ifm system solutions...

Страница 92: ...w of the installed ifm apps The following information is displayed for each ifm app Information Meaning Name Designation of the ifm system solution app Version Version number of the ifm system solutio...

Страница 93: ...name of the selected single basic app is displayed 3 Transfer the single basic app to the device Click on Transfer file button to transfer the selected single basic app to the device The progress bar...

Страница 94: ...le name of the selected multi app is displayed 3 Transfer the multi app onto the device Click on Transfer file to transfer the selected multi app onto the device The progress bar indicates the status...

Страница 95: ...out installed ifm apps S 92 1 Download new ifm app Download new version of the ifm system solution Notes on ifm system solutions S 91 2 Update the installed ifm app Install the new ifm system solution...

Страница 96: ...rical connection of the device Operating instructions supplied with the device 6 1 Connect the device to the periphery 41574 6 1 1 EtherNet IP interface 41494 To connect the device to a PROFINET netwo...

Страница 97: ...tart screen Page view S 19 6 2 1 Change the basic settings of the device 41597 To change the basic settings of the device 1 Start the device Connect the device to a circuit The device starts The displ...

Страница 98: ...ition at a time Save the changes with Finish and go to the standard start screen Option 2 Synchronise the system time with an NTP server Activate the checkbox NTP aktivieren Status LED Enter the IP ad...

Страница 99: ...ng data record Path to the menu page User language of the GUI System Setup System settings Display settings screen saver return System Setup System settings System time date time System Setup Clock NT...

Страница 100: ...neously Press the left function key and the arrow keys and simultaneously and keep them pressed picture Connect the device to a circuit Keep the keys pressed until the screen ifm Recovery appears appr...

Страница 101: ...a circuit Keep the keys pressed until the screen ifm Recovery appears approx 10 s 3 Optional adjust the IP parameters Use the arrow keys to select the menu item Network Setup Press OK to go to the ne...

Страница 102: ...etwork setup with Back The display shows the ifm Recovery page 4 Update the firmware Access the web interface of the device The web interface of the recovery mode appears Press the Search button The f...

Страница 103: ...ed information on the configuration of the PROFINET network Operating instructions of the PROFINET master To integrate the device into a PROFINET network 1 Set interface parameters Set interface param...

Страница 104: ...e in the operating mode protected mode Requirements The new and the old AS i slave have the same device profile Profiles of AS i slaves S 122 The new AS i slave has the address 0 Parameter Automat adr...

Страница 105: ...sition of the status LED on device Overview S 11 7 1 1 Status LED Basic device 41691 Status LED Description H1 green on Device has started warnings or error messages yellow flashes 0 5 Hz There is a w...

Страница 106: ...ne This function is only available via the web interface of the device Remote access S 32 7 2 2 Operating mode of the AS i master 41722 Status LED Description AS i 1 2 operating mode yellow on project...

Страница 107: ...er action required Event An uncritical event has occurred No user action required 7 3 2 Locate error sources 41743 The online diagnosis function helps the operator to locate the source of ooccuring wa...

Страница 108: ...lures and errors The OSC has the following appearance List to select a filter and name of the selected filter Message An message consists of error symbol timestamp and detailed information about the e...

Страница 109: ...nt tab 2 Show current messages The page shows the error messages that are currently active Press to select the message field The focus orange frame is on the message field Use to go through the error...

Страница 110: ...at which the error occurred Time at which the cause of the fault was rectified To display the history of messages created so far again 1 Select menu page On the start screen Select OSC Select History...

Страница 111: ...assignment in Ethernet networks 114 Configuration interfaces Connection concepts 115 AS i master 117 AS i slaves 121 Fieldbus Profinet 131 OSC messages 170 33879 8 1 Approval tests certifications 4152...

Страница 112: ...m steel sheet Makrolon Dimensions W x H x D mm 93 x 128 2 x 106 2 8 2 2 Power supply connections 41800 Power supply connections AS i 1 AS i 2 FE plug in 6 poles Combicon 24 V Power supply plug in 2 po...

Страница 113: ...integrated 2 port switch iRT compatible 41491 SD card slot Media SD memory cards max 32 Gbytes Format SDHC format is supported Supported file formats FAT32 8 2 6 Programmable Logic Controller PLC 4177...

Страница 114: ...same physical network different subnet masks of the participants are allowed They form different groups of participants which cannot communicate with groups of participants having other subnet masks I...

Страница 115: ...d to the necessary IT infrastructure The device supports the following connection types Direct connection S 115 Connection via Ethernet network S 116 8 4 1 Direct connection 42925 Connect either confi...

Страница 116: ...that the data exchange between both devices is ensured Address assignment in Ethernet networks S 114 Connect the PC laptop to the switch using an Ethernet cable User can access the web interface and...

Страница 117: ...device interface 117 8 5 AS i master Content Operating modes of the AS i master 118 Master flags 120 41540 Master Handles the complete organisation on the bus The master decides on the bus access time...

Страница 118: ...s of the AS i master S 49 Automatic addressing When a defective slave is replaced the AS i master controls the addressing The new AS i slave obtains the same address as the old AS i slave if the follo...

Страница 119: ...f the AS i master as follows per GUI web interface Set the operating mode of the AS i master S 48 per function block Set_Mode programming manual Set_Mode If an AS i slave with the address 0 is connect...

Страница 120: ...38 The master flags contain information about the status of the AS i master and the fieldbus host The master flags are transmitted along with the input data of the digital AS i slaves in the acyclic d...

Страница 121: ...Profinet device interface 121 8 6 AS i slaves Content Profiles of AS i slaves 122 41533 Slave Passive participant on the bus only replies on request of the master Slaves have a clearly defined and uni...

Страница 122: ...8 6 1 Profilesof AS i slaves Content Configuration data CDI of the slaves slave profiles 123 Slave profiles for slaves with combined transaction 129 Combined transaction Use of analogue channels in t...

Страница 123: ...profile has the following structure S IO code ID code ext ID code2 Bits 15 12 Bits 11 8 Bits 7 4 Bits 3 0 XID2 extended ID code 2 3rd figure in the slave profile AS i slave v2 0 0xF XID1 extended ID...

Страница 124: ...ut output output F 1111 not allowed Description of the ID code selection 41589 Structure slave profile S x ID Code x ID code hex ID code Bits 3 0 Description 0 0000 4 I O connections for binary sensor...

Страница 125: ...nsparent data exchange binary bits 1 analogue value transmission 0 output slave 1 input slave The ID code 2 results from a combination of the options stated above Extended ID code 2 for analogue slave...

Страница 126: ...ata bits by using 2 3 or 4 slave addresses in a slave 7 0 F motor starter 2I 2O e g ZB0032 7 0 E 4 binary inputs 4 binary outputs e g I O module AC2251 7 1 x interface for the transmission of 6 18 bit...

Страница 127: ...ND 2 safe binary outputs AND 2 non safe relay outputs e g I O module AC009S 7 D x device for motor control electromechanical 7 D 0 electromechanical motor control with open sub profile 7 D 1 electrome...

Страница 128: ...igital bits D0 D3 another part via the analogue channels The more data is transmitted the longer it takes until all data of a slave has been transmitted Cycle time single slave 5 ms Cycle time A B sla...

Страница 129: ...M4 0 4 I and 0 4 O 0 4 analogue inputs or 65 binary inputs and 0 4 analogue outputs or 65 binary outputs 2 inputs and 2 outputs yes type 2 S 7 A 5 M4 0 2 I and 0 2 O 0 2 analogue inputs or 33 binary...

Страница 130: ...1 a X 7 4 D S 2 a a X 7 4 E S 4 a a a a X CTT2 7 5 5 S 0 4 a b a b a b a b X a b a b a b a b X CTT2 7 A 5 A 0 2 a b a b X a b a b X 7 A 5 B 0 2 a b a b X a b a b X CTT3 7 A 7 A only binary only binar...

Страница 131: ...n via TCP IP and the real time communication for real time requirements in modular plant construction Both ways of communication can be used in parallel Profinet IO has been created for real time RT a...

Страница 132: ...nels per input slave 4 channels For each AS i analogue slave 4 words at data are reserved Slave 1 AS i master 1 Slave 15 AS i master 1 Slave 17 AS i master 1 Slave 31 AS i master 1 Slave 1 AS i master...

Страница 133: ...rameter data are downloaded to the device activated in the AS i slaves and stored non volatilely Param slave 1 A AS i master 1 Param slave 31 A AS i master 1 Param slave 1B AS i master 1 Param slave 3...

Страница 134: ...the AS i slaves and stored non volatilely Param slave 1 A AS i master 1 Param slave 31 A AS i master 1 Param slave 1B AS i master 1 Param slave 31B AS i master 1 Param slave 1 A AS i master 2 Param sl...

Страница 135: ...tal input output data AS i Master 2 for single and A slaves Slot 2 Digital inputs outputs of single A slaves AS i master 2 S 137 3 Digital input output data AS i Master 1 for B slaves Slot 3 Digital i...

Страница 136: ...laves Slot 3 Digital inputs outputs of B slaves AS i master 1 S 138 4 Digital input output data AS i Master 2 for B slaves Slot 4 Digital inputs outputs of B slaves AS i master 2 S 138 5 Analogue inpu...

Страница 137: ...yte data block the data of 8 AS i slaves is transmitted Mapping of the digital input output data S 139 Slot 2 Digital inputs outputs of single A slaves AS i master 2 41616 Slot Description Value range...

Страница 138: ...yte data block the data of 8 AS i slaves is transmitted Mapping of the digital input output data S 139 Slot 4 Digital inputs outputs of B slaves AS i master 2 41636 Slot Description Value range Length...

Страница 139: ...Slave 6B Slave 7 A Slave 7B X X X X 5 Slave 8 A Slave 8B Slave 9 A Slave 9B X X X 6 Slave 10 A Slave 10B Slave 11 A Slave 11B X X X 7 Slave 12 A Slave 12B Slave 13 A Slave 13B X X X 8 Slave 14 A Slav...

Страница 140: ...digital input data contain the master flags They provide information on the operating state of the AS i master Bit 7 Bit 6 Bit 5 Bit 4 AS i power fail 19 V Configuration error in the AS i system AS i...

Страница 141: ...uts 20 024 words 24 words analogue inputs 24 028 words 28 words analogue inputs 28 032 words 32 words analogue inputs 32 036 words 36 words analogue inputs 36 040 words 40 words analogue inputs 40 044...

Страница 142: ...words analogue outputs 16 020 words 20 words analogue outputs 20 024 words 24 words analogue outputs 24 028 words 28 words analogue outputs 28 032 words 32 words analogue outputs 32 036 words 36 words...

Страница 143: ...slave assignment for slots 5 6 S 144 A configuration of the slave order in the device specific parameters is ineffective 2 channels Fixed slave assignment Channels 1 and 2 of the slave addresses 1 to...

Страница 144: ...ster 1 slave 13 A Channel 1 AS i master 1 slave 7 A Channel 1 14 AS i master 1 slave 14 A Channel 1 AS i master 1 slave 7 A Channel 2 15 AS i master 1 slave 15 A Channel 1 AS i master 1 slave 8 A Chan...

Страница 145: ...1 48 AS i master 2 slave 18 A Channel 1 AS i master 1 slave 24 A Channel 2 49 AS i master 2 slave 19 A Channel 1 AS i master 1 slave 25 A Channel 1 50 AS i master 2 slave 20 A Channel 1 AS i master 1...

Страница 146: ...i master 2 slave 14 A Channel 1 90 AS i master 2 slave 14 A Channel 2 91 AS i master 2 slave 15 A Channel 1 92 AS i master 2 slave 15 A Channel 2 93 AS i master 2 slave 16 A Channel 1 94 AS i master 2...

Страница 147: ...30 A Channel 2 123 AS i master 2 slave 31 A Channel 1 124 AS i master 2 slave 31 A Channel 2 Table Variable slave assignment for slots 5 6 41182 The following table shows the structure of the data im...

Страница 148: ...A slave Single or A slave 0 Input 1 Channel analogue input B slave B slave 0 2 Channels analogue input single or A slave Single or A slave 0 1 2 Channels analogue input B slave B slave 0 1 4 Channels...

Страница 149: ...4 words AC1403 04 SPS fieldbus PLC 24 028 words 28 words AC1403 04 SPS fieldbus PLC 28 032 words 32 words AC1403 04 SPS fieldbus PLC 32 036 words 36 words AC1403 04 SPS fieldbus PLC 36 040 words 40 wo...

Страница 150: ...4 words fieldbus PLC AC1403 04 SPS 24 028 words 28 words fieldbus PLC AC1403 04 SPS 28 032 words 32 words fieldbus PLC AC1403 04 SPS 32 036 words 36 words fieldbus PLC AC1403 04 SPS 36 040 words 40 wo...

Страница 151: ...uts 16 A 31 B DS4 r 80 35 0 63 M1 digital slave outputs 1 A 31 A and 1B 31B 1 byte per slave DS5 r w 32 36 0 119 M1 analogue slave outputs 1 A 15 B DS6 r w 60 37 0 127 M1 analogue slave outputs 16 A 3...

Страница 152: ...32 71 0 31 M2 LAS LDS LPF LCE DS9 r 16 72 0 7 M2 LPS DS10 r 4 73 0 127 M2 current configuration data CDI DS11 r 64 74 0 127 M2 projected configuration data PCD DS12 r 64 75 0 63 M2 input parameter im...

Страница 153: ...S8 Statusflags of analogue output data of slaves 1 A 31 A and 1B 31B r 32 DS9 Slave lists LAS LDS LPF LCE r 16 DS10 Slave list LPS r 4 DS11 Actual Configuration data CDI r 64 DS12 Projected Configurat...

Страница 154: ...265 Set the date time 010A 266 Configure the NTP server settings 010B 267 Read date time NTP settings 010C 268 Reboot the system 010D 269 Read fieldbus information can only be executed in CODESYS 010F...

Страница 155: ...andard write call of an AS i slave with CTT2 profile CTT2 slave profile 0026 38 CTT2 vendor specific read acyclic manufacturer specific read call of an AS i slave with CTT2 profile CTT2 slave profile...

Страница 156: ...5 5 S 7 A 5 or S B A 5 CTT Combined transaction Use of analogue channels in the gateway depending on the slave profile S 129 Detailed information about the acyclic data sets and the command interface...

Страница 157: ...in this fieldbus I M0 is absolutely necessary for the certification I M data addressing 41468 Revision 2011 11 16 The I M data can be read from the device or write to the device with the following add...

Страница 158: ...th 0x20 blank HARDWARE_REVISION 2 e g AA Device version 2 ASCII characters SOFTWARE_REVISION 4 e g V3 0 8 e g V3 0 8 Byte 0 software type char V official release Byte 1 major version uint8 3 Byte 2 mi...

Страница 159: ...re application specific For this reason the manufacturer does not implement process alarms in this device Diagnosis alarms 41449 Diagnosis alarms are used where an error or event occurs in the device...

Страница 160: ...ter number 0x03 SLA configuration error too many slaves M 1 0x8000 master number slave address 0x04 SLA configuration error slave missing M 1 0x8000 master number slave address 0x05 SLA configuration...

Страница 161: ...g 165 Alarm 0x05ss configuration error slave has an incorrect profile 166 Alarm 0x06ss periphery fault 167 Alarm 0x07ss double addressing fault 168 41463 After an incoming alarm the data for the diagn...

Страница 162: ...S i master set to the projection mode 41564 Offset Word no Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 reserved M Legend M master no 1 bit 0 AS i master 1 1 AS i master 2 Alarm 0x0203 new slave 0 was...

Страница 163: ...V Offset Word no Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 reserved M Legend M master no 1 bit 0 AS i master 1 1 AS i master 2 Alarm 0x0208 19 V AS i power failure detected 41560 Supply voltage of t...

Страница 164: ...29 9B 778 030A 10 A 810 032A 10B 779 030B 11 A 811 032B 11B 780 030C 12 A 812 032C 12B 781 030D 13 A 813 032D 13B 782 030E 14 A 814 032E 14B 783 030F 15 A 815 032F 15B 784 0310 16 A 816 0330 16B 785 0...

Страница 165: ...0A 10 A 1066 042A 10B 1035 040B 11 A 1067 042B 11B 1036 040C 12 A 1068 042C 12B 1037 040D 13 A 1069 042D 13B 1038 040E 14 A 1070 042E 14B 1039 040F 15 A 1071 042F 15B 1040 0410 16 A 1072 0430 16B 1041...

Страница 166: ...1290 050A 10 A 1322 052A 10B 1291 050B 11 A 1323 052B 11B 1292 050C 12 A 1324 052C 12B 1293 050D 13 A 1325 052D 13B 1294 050E 14 A 1326 052E 14B 1295 050F 15 A 1327 052F 15B 1296 0510 16 A 1328 0530 1...

Страница 167: ...78 062A 10B 1547 060B 11 A 1579 062B 11B 1548 060C 12 A 1580 062C 12B 1549 060D 13 A 1581 062D 13B 1550 060E 14 A 1582 062E 14B 1551 060F 15 A 1583 062F 15B 1552 0610 16 A 1584 0630 16B 1553 0611 17 A...

Страница 168: ...03 3 1796 0704 4 1797 0705 5 1798 0706 6 1799 0707 7 1800 0708 8 1801 0709 9 1802 070A 10 1803 070B 11 1804 070C 12 1805 070D 13 1806 070E 14 1807 070F 15 1808 0710 16 1809 0711 17 1810 0712 18 1811 0...

Страница 169: ...us controller an interrupt of the cyclic program OB1 processing is automatically generated 3 In this case the Simatic operating system calls the OB82 diagnostics alarm OB which allows specific alarm p...

Страница 170: ...nuell SPS Event not necessary System power up completed SW Version Event not necessary A system reset was requested manually Event not necessary The user specific message history was deleted Event not...

Страница 171: ...ork Readdress the remaining AS i slave Reconnect removed AS i slave to the AS i network The automatic addressing is not activated for AS i 1 2 Warning Activate automatic addressing AS i1 AS i2 Master...

Страница 172: ...tion interface 96 Configuration interfaces Connection concepts 115 Configuration of the analogue channels in the slots 5 6 143 Configure the IP parameters automatically 82 Configure the IP parameters...

Страница 173: ...he language with a key combination 69 OSC Show message history 110 View current error messages 109 OSC messages 170 AS i 1 AS i 2 171 System 170 Overview 11 acyclic data sets DSx 153 Acyclic process d...

Страница 174: ...slaves AS i master 2 138 Slot 5 Analogue input data 141 Slot 6 Analogue output data 142 Slot 7 Inputs from AC1403 04 SPS 149 Slot 8 Outputs to AC1403 04 SPS 150 Start screen 36 Status LEDs 106 Start s...

Отзывы: