14
9.2 Configuring the display (optional)
►
Select [Uni] and set the unit of measurement:
-[bAr],
-[MPA], [kPA],
-[PSI],
-[InHO] (only PI7096),
-[mWS] (only PI7096)�
►
Select [SELd] and set the display mode:
-[P]: Pressure in the unit set in Uni�
-[P%]: percentage value (pressure in % of the set scaling of the
analogue output� The following applies: 0% = ASP value; 100% = AEP
value)�
NOTE: Display „0%“ does not mean that the system is free of pressure�
►
Select [diS] and set update rate and orientation of the display:
-[d1]: Update of the measured value every 50 ms�
-[d2]: Update of the measured value every 200 ms�
-[d3]: Update of the measured value every 600 ms�
-[rd1], [rd2], [rd3]: Display like d1, d2, d3; rotated by 180°�
-[OFF]: The display is deactivated in the operating mode� If one of the
buttons is pressed, the current measured value is displayed for 15 s�
Another press of the Mode/Enter button opens the Display mode� The
LEDs remain active even if the display is deactivated�
9.3 Setting the output signal
9.3.1 Setting the output function
►
Select [OU1] and set the switching function:
-[Hno] = hysteresis function / normally open,
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function / normally closed�
As an alternative: configure OUT1 as diagnostic output:
►
Select [OU1] and set [dESI]�
►
Select [OU2] and set the switching function:
-[Hno] = hysteresis function / normally open,
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function / normally closed�