9 Parameter setting
During parameter setting the unit remains in the operating mode� It continues its
monitoring function with the existing parameters until the parameter setting has
been completed�
Exceptions: changes to the parameters COF (→ 9.4.1), CP1 and CP2 (→ 9.4.6) take effect
immediately�
9.1 General parameter setting
3 steps must be taken for each parameter setting:
1
Select parameter
►
Touch [Mode/Enter] until the
requested parameter is displayed
.
Mode/
Enter
Set
2
Set parameter value
►
Touch [Set] and keep it touched�
> Current setting value of the
parameter flashes for 5 s�
> After 5 s: setting value is changed:
step by step by touching briefly
several times or continuously by
touching permanently�
Mode/
Enter
Set
Numerical values are incremented continuously� To reduce the value: let the display
move to the maximum setting value� Then the cycle starts again at the minimum
setting value�
3
Acknowledge parameter value
►
Touch [Mode/Enter] briefly�
> The parameter is displayed again�
The new setting value is saved�
Mode/
Enter
Set
Set other parameters
►
Start again with step 1�
Finish parameter setting
►
Touch [Mode/Enter] several times until the current measured value is displayed or wait
for 15 s�
> The unit returns to the operating mode�
• Timeout:
If no touch button is activated for 15 s during parameter setting, the unit returns to the
operating mode with unchanged values�