10.4 Extended functions
10.4.1 Setting of the time delay for switching outputs
►
Select [EF]�
►
Press [SET] to change to the menu [EF]�
►
Select parameters with [MODE/ENTER]:
[dSx] = switch-on delay; [drx] = switch-off delay
►
Set the parameter value with [SET]:
Setting range [s]: 0 / 0�1 ��� 5 s in steps of 0�1s
(0 = delay time is not active)
►
Confirm with [MODE/ENTER]�
10.4.2 Setting of the fault suppression time for switching outputs / analogue
output
►
Select [EF]�
►
Press [SET] to change to the menu [EF]�
►
Select [dFo] (formely: [dAP])�
►
Set the parameter value with [SET]:
Setting range [s]: 0���0�1���0�2���0�5���1���2���5�
►
Confirm with [MODE/ENTER]�
With [dFo], the error types "too much light" and "not enough light" are
�
10.4.3 Reset of all parameters to factory setting
►
Select [EF]�
►
Press [SET] to change to the menu [EF]�
►
Select [rES], then press [SET] and keep it pressed until [----] is
displayed�
►
Confirm with [MODE/ENTER]�
> The unit changes to the Run mode�
10.4.4 Display of the software version number
►
Select [EF]�
►
Press [SET] to change to the menu [EF]�
►
Select [SW], then press [SET]�
> The software version number is displayed�
►
Press [MODE/ENTER] to return to the menu [EF]�