Operating instructions 

Optical distance sensor

O1D102

80262529 / 00

 

 03 / 2017

UK

Содержание O1D102

Страница 1: ...Operating instructions Optical distance sensor O1D102 80262529 00 03 2017 UK ...

Страница 2: ...cessories 7 6 Electrical connection 8 6 1 Operation with IO Link master 8 7 Operating and display elements 9 8 Menu 10 8 1 Menu structure 10 8 2 Explanation of the menu 11 9 Operating modes 13 9 1 Run mode 13 9 2 Display mode 13 9 3 Object reflectivity 13 9 4 Programming mode 13 10 Parameter setting 14 10 1 Parameter setting in general 14 10 1 1 Setting of the parameter value 14 10 1 2 Change from...

Страница 3: ... mode 22 10 3 1 Setting of the sampling rate 22 10 3 2 Setting of the repeatability 22 10 3 3 Table repeatability and accuracy 22 10 4 Extended functions 23 10 4 1 Setting of the time delay for switching outputs 23 10 4 2 Setting of the damping of the measured signal 23 10 4 3 Reset of all parameters to factory setting 23 10 4 4 Display of the software version number 23 11 IO Link 24 11 1 General ...

Страница 4: ...ns Please read this document prior to set up of the unit Ensure that the product is suitable for your application without any restrictions Improper or non intended use may lead to malfunctions of the unit or to unwanted effects in your application That is why installation electrical connection set up operation and maintenance of the unit must only be carried out by qualified personnel authorised b...

Страница 5: ...esult in hazardous radiation exposure Damage to the retina is possible Do not stare into the laser beam Apply the enclosed labels laser warning in the immediate vicinity of the unit Adhere to the caution and warning notes on the product label Use the enclosed label for the power supply cable Label for supply cable Product label ...

Страница 6: ...eresis The hysteresis keeps the switching state of the output stable if the measured value varies about the sensing range Both outputs OUT1 and OUT2 can be set as hysteresis function 10 2 4 Hysteresis function 4 2 Output function window The window function enables the monitoring of a defined acceptable range Both outputs OUT1 and OUT2 can be set as window function 10 2 6 Window function 4 3 Analog...

Страница 7: ...uous 5 2 Mounting accessories The unit is supplied without mounting accessories Examples of mounting accessories Art no Protective cover O1D E21133 Mounting set E2D101 E20938 E20951 E21079 Mounting set O1D for rod mounting Ø 12 mm E2D101 Mounting rod straight Ø 12 mm M10 E20938 Mounting set O1D for rod mounting Ø 14 mm E2D111 Mounting rod straight Ø 14 mm M12 E20939 Fixture for mounting and fine a...

Страница 8: ... Operation with IO Link master The unit is compatible with IO Link master port class A type A For operation with IO Link master port class B type B observe the following As a standard the unit is not compatible with master port class B type B Pin 2 OU2 and pin 5 IN1 are used for manufacturer specific functions That means that the main supply voltage of the unit and the additional voltage supply ma...

Страница 9: ...us lights if the corresponding output is switched 3 4 digit alphanumeric display Indication of the measured distance the parameters and parameter values 4 Programming button SET Setting of the parameter values scrolling by holding pressed incrementally by pressing once 5 Programming button MODE ENTER Selection of the parameters and acknowledgement of the parameter values ...

Страница 10: ...10 8 Menu 8 1 Menu structure MODE ENTER SET ...

Страница 11: ...Fno or Fnc 10 2 7 Setting of the switch points for window function OUT1 Configuration for output 2 4 switching functions and 2 analogue signals can be selected Hno Hnc Fno Fnc I U 10 2 8 Configuration of OUT2 Switch point for hysteresis function OUT2 Limit value at which the output with selected hysteresis function changes its switching state object nearer farther than distance set SP2 is only act...

Страница 12: ...and dr2 are not effective if OU2 I or U 10 4 1 Setting of the time delay for switching outputs Damping of the measured signal This function allows to suppress short time saturation of the measuring element such saturation can result from direct reflection or strong fluctuations in brightness During the delay set the latest valid value measured is displayed the output signals remain unchanged 10 4 ...

Страница 13: ...NTER briefly Unit goes to the Display mode Internally it remains in the operating mode The set parameter values can be read To scroll through the parameters press MODE ENTER briefly To display the respective parameter value press SET briefly After 15 s the unit returns to the Run mode 9 3 Object reflectivity Display of the object reflectivity formerly align mode Press SET in the Run mode The unit ...

Страница 14: ...election of the parameter Press MODE ENTER until the requested parameter is displayed 2 Setting of the parameter value Press SET and keep it pressed The current parameter value flashes for 5 s Increase the setting value incrementally by pressing the button once or continuously by pressing it permanently Decrease the value let the display move to the maximum setting value Then the cycle starts agai...

Страница 15: ...s On delivery the unit is not locked Locking Make sure that the unit is in the normal operating mode Keep MODE ENTER SET pressed until Loc is displayed The unit is locked Loc is displayed briefly if you try to change parameter values on the locked unit during operation Unlocking Keep MODE ENTER SET pressed until uLoc is displayed The unit is unlocked Timeout If no button is pressed for 15 s during...

Страница 16: ...ngs can be selected d1 update of the measured value every 50 ms d2 update of the measured value every 200 ms d3 update of the measured value every 600 ms rd1 rd2 rd3 display like d1 d2 d3 rotated by 180 The update of the measured value only refers to the display It has no effect on the outputs OFF The measured value display is deactivated in the Run mode Press one button to indicate the current me...

Страница 17: ...afety factor of 1 5 10 3 3 Table repeatability and accuracy Example Hno 1 For the output function Hno the output switches when the object approaches and when the switch point A is reached 2 When the object is removed again the output does not switch back before the reset point B is exceeded The reset point B is greater than the set point A 1 2 SPx switch point A set point B reset point When the ou...

Страница 18: ...1200 mm 14 mm 1186 mm 10 2 5 Setting of the switch point for hysteresis function OUT1 Select the output function Hno or Hnc at OU1 Confirm with MODE ENTER Select SP1 and set the switch point Confirm with MODE ENTER 10 2 6 Window function It is possible to define a window for the object recognition for each of the two outputs OUT1 OUT2 Switches off when the object is detected nSPx switch point near...

Страница 19: ...utput status Fno D nSPx Open D FSPx nSPx D FSPx Closed Fnc D nSPx Closed D FSPx nSPx D FSPx Open Both window limit values nSPx and FSPx work with a switching hysteresis 10 2 4 Hysteresis function example of the output function Hno 10 2 7 Setting of the switch points for window function OUT1 Select the output function Fno or Fnc at OU1 Confirm with MODE ENTER Select nSP1 and set the switch point ne...

Страница 20: ...OUT2 Select Fno or Fnc at OU2 Confirm with MODE ENTER Select nSP2 and set the switch point near Confirm with MODE ENTER Select FSP2 and set the switch point far Confirm with MODE ENTER 10 2 6 Window function 10 2 11 Scaling of the measuring range analogue output Select I or U at OU2 Confirm with MODE ENTER Select ASP and set Analogue start point With ASP you define at which measured value the outp...

Страница 21: ...ults are also displayed Too much light or object too near 3 5 mA for a rising edge ASP AEP 20 5 mA for a falling edge ASP AEP Object too far or no object present 20 5 mA for a rising edge 3 5 mA for a falling edge Voltage output 0 10 V Factory setting Measuring range scaled MEW final value of the measuring range In the set measuring range the output signal is between 0 and 10V ...

Страница 22: ...e repeatability rEPr are displayed alternately 10 3 2 Setting of the repeatability Select TEAC then press SET and keep pressed until WAIT is displayed rATE and rEPr are displayed alternately When rEPr is displayed Press SET until the preset repeatability value flashes Enter value incrementally by pressing SET once Confirm with MODE ENTER WAIT is displayed while the sampling rate rATE is calculated...

Страница 23: ...irm with MODE ENTER 10 4 2 Setting of the damping of the measured signal Select EF Press SET to change to the menu EF Select dFo formely dAP Set the parameter value with SET Setting range s 0 0 1 0 2 0 5 1 2 5 Confirm with MODE ENTER 10 4 3 Reset of all parameters to factory setting Select EF Press SET to change to the menu EF Select rES then press SET and keep it pressed until is displayed Confir...

Страница 24: ... information and parameters in the overview table at www ifm com uk io link 11 3 Parameter setting tools You will find all necessary information about the required IO Link hardware and software e g ifm LINERECORDER SENSOR ZGS210 at www ifm com uk io link 11 4 Extended functions With IO Link extended functions and measured data are available 11 5 Teach function The following teach functions are ava...

Страница 25: ...r object to be measured outside the measuring range 0 2 m ON OFF OFF ON 3 5 mA 0 V 20 5 mA 10 V UL NoData FAr object to be measured outside the measuring range 3 5 m OFF ON OFF ON 20 5 mA 10 V 3 5 mA 0 V OL NoData Errp plausibility e g object too fast X1 X1 X1 X1 X1 X1 X1 X1 LoFF laser switched off OFF ON OFF ON 20 5 mA 10 V 3 5 mA 0 V NoData NoData SC1 short circuit in switching output 1 2 2 n a ...

Страница 26: ...facturer Keep the front lens of the sensor free from soiling After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations 14 Scale drawing Dimensions in mm 1 4 digit alphanumeric display LED function display 2 programming buttons ...

Страница 27: ...000 nSP1 200 3500 800 FSP1 200 3500 1200 OU2 Hno Hnc Fno Fnc I U I SP2 200 3500 2000 nSP2 200 3500 1800 FSP2 200 3500 2200 ASP 0 3500 0 AEP 0 3500 3500 rATE 1 50 5 Hz dS1 0 0 1 5 0 s dr1 0 0 1 5 0 s dS2 0 0 1 5 0 s dr2 0 0 1 5 0 s dFo 0 0 1 0 2 0 5 1 2 5 0 s diS d1 3 rd1 3 OFF d3 Technical data and further information at www ifm com ...