12.8 Output response in different operating states
OUT1
OUT2*
Initialisation
OFF
OFF
Normal operation
according to the level and
[ou1] setting
according to the level 4...20
mA
Fault
OFF for [FOU1] = [OFF]
ON for [FOU1] = [On]
< 3.6 mA at [FOU2] = [OFF]
> 21 mA at [FOU2] = [On]
* If the analogue function [ou2] = [I] has been selected.
If the switching function has been selected: see column OUT1
Additional information about the analogue output:
Full signal: With [ou2] = [I]:
20...20.5 mA
With [ou2] = [InEG]: 4...3.8 mA
Empty signal: With [ou2] = [I]:
4...3.8 mA
With [ou2] = [InEG]: 20...20.5 mA
13 Technical data
Technical data and scale drawing at www.ifm.com
13.1 Setting ranges
[LEnG]
mm
Setting range
150...2000
Step increment
5
The setting ranges for the switching limits ([SPx], [rPx], [FHx], [FLx]) depend on
the probe length (L). In general the following applies:
mm
min
max
[SPx] / [FHx]
15 (35)
L - 30
[rPx] / [FLx]
10 (30)
L - 35
Step increment
1
Note: The values in brackets apply to the setting [MEdl] = [LOW) (→ 11.2.3)
• [rPx] / [FLx] is always smaller than [SPx] / [FHx]. If [SPx] / [FHx] is shifted, [rPx ] / [FLx] also
shifts provided that the lower end of the setting range is not reached. Always set [SPx] /
[FHx] first, then [rPx] / [FLx].