40
►
Select [FLx] and set the lower limit of the acceptable range.
[FLx] is always lower than [FHx]. The unit only accepts values which are
lower than the value for [FHx].
11.4.4 Set switch-on delay for switching outputs
►
Select [dSx] and set the value between 0.0 and 60 s.
The switch-on delay reacts according to VDMA*
)
.
11.4.5 Set switch-off delay for switching outputs
►
Select [drx] and set the value between 0.0 and 60 s.
The switch-off delay reacts according to VDMA*).
*
)
According to VDMA the switch-on delay always has an effect on SP, the switch-off delay
always on rP irrespective of whether the normally open or normally closed function is used.
11.4.6 Set output function for OUT2
► Select [ou2] and set the switching function:
[I] =
Current output 4...20 mA
[InEG] =
Current output 20...4 mA
[Hno] =
Hysteresis function / normally open
[Hnc] =
Hysteresis function / normally closed
[Fno] =
Window function / normally open
[Fnc] =
Window function / normally closed
Note: If the switching output is used as an overflow prevention, the setting
[ou2] = [Hnc] (normally closed function) is recommended. The
principle of normally closed operation ensures that wire break or cable
break is also detected.
11.4.7 Scale analogue signal
►
Select [ASP2] and set the analogue start point.
►
Select [AEP2] and set the analogue end point.
These parameters can only be set via an IO-Link device tool if the
parameter [ou2] is set to [I] or [InEG].
11.4.8 Set output logic for switching outputs
►
Select [P-n] and set [PnP] or [nPn].