11.2 Basic settings (set-up)
On delivery of the unit, you must first enter the basic settings. The complete user
menu then opens.
11.2.1 Enter type of probe used
►
Apply operating voltage.
> The initial display
is shown.
► Select [Prob] and set:
►
Press [Enter].
> [nonE] is displayed.
►
Press [
▲
] or [
▼
] for min. 1 s and set the value:
[rod] =
Single probe, for the detection of:
-water and water-based media.
[COAX] =
Coaxial probe, for the detection of:
-oils and oil-based media.
-water and water-based media.
►
Press [Enter].
• The detection of water and water-based media is possible with the single
probe as well as with the coaxial probe.
• The detection of oils and oil-based media is only possible with the coaxial
probe.
11.2.2 Enter probe length
►
Select [LEnG].
►
Press [Enter].
> [nonE] is displayed.
►
Press [
▲
] or [
▼
] for at least 1 s.
> After 1 s the unit automatically displays the detected probe length
(preset function*).
►
Correct the probe length, if necessary, with [
▲
] or [
▼
]. Incrementally by
pressing the button once or continuously by keeping the button pressed.
Enter the probe length in mm.
►
Press [Enter].
*)
Automatic probe length detection is only possible with empty tank and sufficiently large
launching plate.
For manual determination of the probe length: (→ 7.5.2)