10.2 Explanation of the menu
10.2.1 Main menu [I]
tREF
Carry out tank adjustment.
Menu item only visible if [LEnG] ≥ 260 mm and [Prob] = [rod].
SP1 / rP1
Set point 1 / reset point 1 at which OUT1 switches.
Menu item only visible if hysteresis function is selected ([ou1] = [H..]).
FH1 / FL1
Upper / lower limit for the acceptable range within which OUT1 switches.
Menu item only visible if window function is selected ([ou1] = [F..]).
ASP2
Analogue start point 2: measured value at which the analogue start value is
provided. The analogue start value is set with parameter [ou2]. Menu item
only visible if analogue output is selected ([ou2] = [I] or [InEG]).
AEP2
Analogue end point 2: measured value at which the analogue end value is
provided. The analogue end value is set with parameter [ou2]. Menu item
only visible if analogue output is selected ([ou2] = [I] or [InEG]).
SP2 / rP2
Set point 2 / reset point 2 at which OUT2 switches.
Menu item only visible if hysteresis function is selected ([ou1] = [H..]).
FH2 / FL2
Upper / lower limit for the acceptable range within which OUT2 switches.
Menu item only visible if window function is selected ([ou1] = [F..]).
EF
┘
Extended functions / opening of menu level 2
10.2.2 EF level (extended functions) [II]
rES
Restore the factory setting.
CFG
┘
Open the submenu CFG (configuration).
ENV
┘
Open the submenu ENV (environment parameter).
SIM
┘
Open the submenu SIM (simulation).