5.3 Installation in pipes
The unit can be installed in pipes using adapters�
Information about the available adapters at www�ifm�com�
1� Screw the adapter (B) into the pipe (A)�
2� Place the seals (C) and install the unit according to the marked flow direction�
►
To mount the adapters on the process connection of the sensor use
suitable lubricants�
3� Screw the adapter (B) with the threads (D) until it is hand-tight�
4� Tighten the two adapters in opposite direction (tightening torque: 30 Nm)�
After installation air bubbles in the system can affect the measurement�
Corrective measures:
►
Rinse the system after installation for ventilation (rinsing quantity > 5 gpm;
< 20 l/min)�