10.4.5 Time-controlled counter-reset
► Select [rTo] and set the requested value (intervals of hours, days or
weeks)�
> The counter is reset automatically with the value now set�
10.4.6 Deactivation of the counter reset
► Select [rTo] and set [OFF]�
> The meter is only reset after overflow (= factory setting)�
10.4.7 Configure counter reset using an external signal
► Select [OU2] and set [InD]�
► Select [DIn2] and set the reset signal:
-[HIGH] = reset for high signal,
-[LOW] = reset for low signal,
-[+EDG] = reset for rising edge,
-[-EDG] = reset for falling edge�
10.5 Settings for temperature monitoring
10.5.1 Settings for limit value monitoring with OUT2
► Select [SEL2] and set [TEMP]�
► Select [OU2] and set the switching function�
-[Hno] = hysteresis function/NO,
-[Hnc] = hysteresis function/NC,
-[Fno] = window function/NO,
-[Fnc] = window function/NC�
► Select [SP2] and set the value at which the output switches�
► Select [rP2] and set the value at which the output switches off�
10.5.2 Setting the analogue value for temperature
► Select [SEL2] and set [TEMP]�
► Select [OU2] and set the function:
-[I] = temperature-proportional current signal (4…20 mA);
-[U] = temperature-proportional voltage signal (0…10 V)�
► Select [ASP2] and set the value at which the minimum value is provided�
► Select [AEP2] and set the value at which the maximum value is pro-
vided�