10.3.2 Settings for limit value monitoring with OUT2
► Select [SEL2] and set [FLOW]�
► Select [OU2] and set the switching function�
-[Hno] = hysteresis function/NO,
-[Hnc] = hysteresis function/NC,
-[Fno] = window function/NO,
-[Fnc] = window function/NC�
► Select [SP2] and set the value at which the output switches�
► Select [rP2] and set the value at which the output switches off�
10.3.3 Setting the analogue value for volumetric flow
► Select [SEL2] and set [FLOW]�
► Select [OU2] and set the function:
-[I] = current signal proportional to volumetric flow (4…20 mA);
-[U] = voltage signal proportional to volumetric flow (0…10 V)�
► Select [ASP2] and set the value at which the minimum value is provided�
► Select [AEP2] and set the value at which the maximum value is pro-
vided�
10.3.4 Setting the frequency value for volumetric flow
► Select [OU1] and set [FRQ]�
► Select [FEP] and set the flow value at which the frequency set in FrEP
is provided�
► Select [FrEP] and set the frequency�
10.4 Settings for consumed quantity monitoring
10.4.1 Settings for quantity monitoring via pulse output
► Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which 1 pulse is
provided (→ 10.4.3).
► Select [ImPR] and set [YES]�
> Pulse repetition is active� Output 1 provides a counting pulse each time
the value set in [ImPS] is reached�