Operating instructions
Flow monitor
SI5010
80000397 / 00
07 / 2014
UK
Страница 1: ...Operating instructions Flow monitor SI5010 80000397 00 07 2014 UK ...
Страница 2: ...O Link 8 7 1 1 General information 8 7 1 2 Device specific information 9 7 1 3 Parameter setting tools 9 7 1 4 Adjustable parameters 9 7 2 Set up and settings for water 10 7 3 Change the switch point optional 10 7 4 High flow adjustment optional 11 7 5 Low flow adjustment optional 11 7 6 Configure the switching output optional 11 7 7 Restore the factory setting reset 12 7 8 Lock unlock the unit 12...
Страница 3: ...personal injury and or damage to property can occur Improper or non intended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connec tion set up operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator In order to guarantee the correct condition of the device for ...
Страница 4: ...If necessary you can change the output to normally closed operation 7 6 It then applies output open if medium is flowing If the flow speed increases the switching status changes when the switch point is reached If the flow speed falls again the switching status changes when the value SP minus hysteresis is reached The hysteresis changes with the flow speed and it is essentially influenced by the s...
Страница 5: ...tion location General The sensor tip is to be completely sur rounded by the medium Immersion depth of the sensor mini mum 12 mm Recommended For horizontal pipes mounting from the side For vertical pipes mounting in the rising pipe Conditional Horizontal pipe mounting from the bottom if the pipe is free from build up Horizontal pipe mounting from the top if the pipe is completely filled with medium...
Страница 6: ...es of interference 4 3 Installation procedure Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the threads of the process connection 1 adapter 2 and nut 3 Note No grease must be applied to the sensor tip A Screw suitable adapter into the process connection Place the flow monitor onto the adapter and ti...
Страница 7: ...ply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows P L 1 4 3 2 L Pin 1 Ub Pin 2 Programming wire for remote setting Pin 3 Ub Pin 4 OUT1 PNP switching signal for flow monitoring IO Link Only use 4 wire sockets without bridge between pin 2 and pin 4 If 3 wire sockets with a bridge between pin 2 and pin 4 are used power on of the output stage triggers the remote calibrat...
Страница 8: ...on If you change parameters during operation this will influence the function Ensure that there will be no malfunctions in your plant 7 1 IO Link 7 1 1 General information This unit has an IO Link communication interface which requires an IO Link capa ble module IO Link master for operation The IO Link interface enables direct access to the process and diagnostic data and provides the possibility ...
Страница 9: ...ng tools You will find all necessary information about the required IO Link hardware and software at www ifm com gb io link 7 1 4 Adjustable parameters SP1 rP1 Upper lower limit value for flow at which OUT1 switches OU1 Output configuration OUT1 Set_High Reading of the maximum flow 100 Set_Low Reading of the minimum flow 0 dS1 dr1 Switch on delay switch off delay for OUT1 Loc Locks sensor operatio...
Страница 10: ...tment 7 4 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 7 4 You can restore the factory setting any time 7 7 7 3 Change the switch point optional For the factory setting the switch point is at LED 7 A change makes sense in the following cases the display shows example 2 the flow fluctuates much or pulsates if a faster response time ...
Страница 11: ...adjustment must only be carried out after the high flow adjustment Let the minimum flow circulate in the installation or ensure flow standstill Press and keep it pressed LED 0 lights after approx 5 s it flashes Release the button The unit adopts the new value and returns to the operating mode 7 6 Configure the switching output optional The unit is delivered as normally open In case of need you can...
Страница 12: ...nit can be adapted to new flow conditions at any time using the remote set ting function Connect Ub to pin 2 for 5 10 s high flow adjustment Connect Ub to pin 2 for 10 15 s low flow adjustment The relative switch point is not shifted 7 10 Switch on switch off delay The unit features an internal switch on switch off delay This serves to delay the release of the outputs OUT1 OUT2 for a set time 0 60...
Страница 13: ...mme diately passes into the normal operating state The current operating state is displayed Display OFF no LED lights Operating voltage too low 19 V or failed Ensure a correct voltage supply Display briefly OFF LEDs go off when a button is pressed The active LEDs go off briefly when a button is pressed if an IO Link communication is active temporary locking or the sensor is permanently locked 7 9 ...
Страница 14: ...the adjustment again The sequence high flow low flow adjust ment was not adhered to Carry out the two adjustment operations again in the right sequence 10 Maintenance Recommended maintenance Check the sensor tip for build up from time to time Clean it using a soft cloth Stubborn build up e g lime can be removed using a common vinegar cleaning agent 11 Technical data Technical data and scale drawin...